Installation Instructions
Vitodens Inox-Radial Heat Exchanger
Cleaning Kit
for use with Vitodens 100, 200 and 222 series
Part No. 7840112
Safety and Installation Requirements
Please ensure that these instructions are read and
understood before starting any service work. Failure to
comply with these instructions may cause product/property
damage, severe personal injury and/or loss of life.
Working on the equipment
The installation, adjustment, service and maintenance of
this product must be performed by a licensed professional
heating contractor who is qualified and experienced in
the installation, service, and maintenance of hot water
boilers. There are no user serviceable parts on the boiler,
burner or control.
Cleaning Instructions
Legend
A Cleaning tool (for between the coils)
B Raised spacers between the coils
C Heat exchanger coils
WARNING
When using the cleaning tool ensure not to gouge
or damage the heat exchanger. Damage may cause
premature failure of the heat exchanger.
5583 487 - 02 12/2024
Ensure that main power to the equipment being serviced
is off.
Ensure that the main fuel supply valve to the boiler is
closed.
Take precautions to avoid accidental activation of power
or fuel during service work.
Do not perform service work on any component part
without ensuring safe operation of the heating system.
When replacing parts, use original Viessmann or
Viessmann approved replacement parts.
Refer to the Installation and Service
Instructions applicable to this boiler.
Following our regular maintenance requirements is
essential to achieve the proper function and performance
of the Viessmann Inox-Radial heat exchanger.
IMPORTANT
Do not use a brush to clean out loose deposits. Brushing
will push the deposits into the spaces between the coils
and could solidify there. The use of additional cleaning
agents is normally not necessary as they could negatively
effect the stainless steel surfaces and clog the spaces
between the coils.
Cleaning the heating surface
1. Vacuum any loose debris from the heat exchanger area.
2. Extremely clogged heat exchanger openings may be
cleaned using the cleaning tool. Gently clean between
the raised spacers of the heat exchanger coils (as
shown).
3. Rinse the heat exchanger area with water.
CAUTION
When rinsing the heat exchanger with water, ensure that
no water makes contact with the controls below.
4. Flush out the condensate trap and condensate drain.
5. Rinse the heat exchanger area with water again.
6. Ensure that the condensate trap is filled with water.