HR1S-AC SAFETY RELAY MODULE OPERATING INSTRUCTIONS
HR1S-AC SAFETY RELAY MODULE OPERATING INSTRUCTIONS
• The module contains electro-mechanical relays. Therefore his
indicated performance level and his MTTF
and on the operating cycles in the application. The above mentioned
performance level and MTTF
d
maximum 6,336 switching cycles per year or for low load and
maximum 316,800 switching cycles per year.
• If the current load is known, use the diagram for the electrical service
life (see page 13/16) to calculate the maximum number of switching
cycles. The specified performance level can only be assured for
the number of switching cycles calculated using this method. The
device must be replaced on reaching this maximum figure.
Thereby the lifetime of the device must not be exceeded.
• Operating the device not within the specifications may lead to
malfunctions or the destruction of the device.
• The supply input A1 serves as a control input. This may lead to short
disruptions or a lowering below the operating voltage U
switch to the release path.
• Expansion devices or external contactors with positively driven
contacts can be used to duplicate the enabling current paths.
• The emergency stop chain must be closed before the reset button is
activated.
• If magnetic switches with reed contacts or sensors with semiconductor
outputs are connected the switch ON peak current must be noticed
(see Technical Data).
• Please consult the installation notes.
Note
Please observe instructions from safety authorities.
Note
Safety systems are comprised of many components. No one safety
component will insure the safety of the system. The design of the
complete safety system should be considered before you begin. It is very
important to follow applicable safety standards when installing and wiring
these components.
There are no user serviceable components in the module. Approved
safety devices must use only the hard contacts outputs between
terminals 13-14, 23-24 and 33-34. The contactless signalling circuit
between terminals Y43-Y44 is permissable only for non-safety related
functions.
It is imperative that an external fuse be connected as shown on the
"WIRING DIAGRAM FOR MODULE HR1S-AC SAFETY RELAY". For
maximum protection of the outputs, please refer to "TECHNICAL DATA"
(page 14/16).
CAUTION
RESIDUAL RISK (EN ISO / ISO 12100-1)
The following wiring diagrams have been tested under actual service
conditions. This module must be used for safety-related functions in
conjunction with the connected safety equipment and devices that meet
applicable standard requirements. A residual risk will remain if:
a) it is necessary to modify this recommended circuit and if the added/
modified components are not properly integrated in the control circuit.
b) the user does not follow the required standards applicable to the
operation of the machine, or if the adjustments to and maintenance of
the machine are not properly made. It is essential to strictly follow the
prescribed machine maintenance schedule.
c) the devices connected to the safety outputs do not have
mechanically-linked contacts.
Failure to follow this instruction can result in injury or equipment
damage.
9 / 16
value depend on the load
d
values are suitable for nominal load and
in order to
B
WARNING
FAILURE TO PROTECT
• Wire safety relay using wiring diagrams provided.
• Wire to meet applicable standards requirements.
• All devices connected to the safety outputs must have mechanically-
linked contacts.
• It is imperative that properly sized external fuses be connected as
shown in wiring diagrams provided.
• Strictly follow prescribed maintenance schedule when making
adjustments to and maintenance of machine.
Failure to follow this instruction can result in death, serious injury,
or equipment damage.
DEUTSCH
GEFAHR
GEFÄHRLICHE SPANNUNG
Die Montage, Inbetriebnahme, Änderung und Nachrüstung darf nur von
einer Elektrofachkraft ausgeführt werden!
Schalten Sie das Gerät/ die Anlage vor Beginn der Arbeiten
spannungsfrei!
Bei Installations und Anlagenfehlern kann bei nicht galvanisch
getrennten Geräten auf dem Steuerkreis Netzpotential anliegen!
Beachten Sie für die Installation der Geräte die Sicherheitsvorschriften
der Elektrotechnik und der Berufsgenossenschaft.
Durch Öffnen des Gehäuses oder sonstige Manipulation erlischt
jegliche Gewährleistung.
Die Nichtbeachtung dieser Anweisung wird Tod oder schwere
Körperverletzung zur Folge haben.
VORSICHT
UNSACHGEMÄSSER GEBRAUCH
Bei unsachgemäßen Gebrauch oder nicht bestimmungsgemäßer
Verwendung darf das Gerät nicht mehr verwendet werden und es
erlischt jeglicher Gewährleistungsanspruch.
Nicht zulässige Einwirkungen können sein:
starke mechanische Belastung des Gerätes, wie sie z.B. beim
Herunterfallen auftritt, Spannungen, Ströme, Temperaturen,
Feuchtigkeit außerhalb der Spezifikation.
Bitte überprüfen Sie gemäß der geltenden Vorschriften bei
Erstinbetriebnahme Ihrer Maschine/ Anlage immer alle
Sicherheitsfunktionen und beachten Sie die vorgegebenen Prüfzyklen
für Sicherheitseinrichtungen.
Die Nichtbeachtung dieser Anweisung kann Körperverletzung
oder Materialschäden zur Folge haben.
VORSICHT
GEFAHR BEI INSTALLATION
Führen Sie vor Beginn der Installation/ Montage oder Demontage
folgende Sicherheitsmaßnahmen durch:
1. Schalten Sie das Gerät/ die Anlage vor Beginn der Arbeiten
spannungsfrei!
2. Sichern Sie die Maschine/ Anlage gegen Wiedereinschalten!
3. Stellen Sie die Spannungsfreiheit fest!
4. Erden Sie die Phasen und schließen Sie diese kurz!
5. Decken und schranken Sie benachbarte, unter Spannung stehende
Teile ab!
6. Der Einbau der Geräte muss in einem Schaltschrank mit einer
Schutzart von mindestens IP 54 erfolgen.
Die Nichtbeachtung dieser Anweisung kann Körperverletzung
oder Materialschäden zur Folge haben.