6. Installation

How to use R718N360
The current conversion formula:
Target load current value= "R718N360 read value" / ("R718N360 read standard load value" / "standard load current value")
When R718N360 is connected to the CT which needs to be used, it is necessary to obtain the conversion coefficient k first.
The acquisition method is to measure a standard load.
The conversion coefficient k= "R718N360 read the standard load value" / "standard load current value"
Example:
The effective current of the standard load measured by R718N360 is 49950mA.
The read value of R718N360 is 165806.
k= 165806 / 49950 = 3.3194394
After obtaining the conversion coefficient k, use R718N360 to measure the target load.
The current value of the target load= "R718N360 read value" / k
Example:
R718N360 reads the value 333162.
The current value of the target load= 333162 / 3.3194394= 100366.9475032mA.
Current Direction
Wire to be
detected
Current Direction
Wire to be
detected
The CT terminal should be
close to the power terminal as
much as possible.
CT
Phase A
CT
Phase B
The CT terminal should be
close to the power terminal
as much as possible.
Installation Diagram
R718N360
Screw
Fixation
Current Direction
CT
Wire to be
detected
8
Screw
Fixation
Phase C
The CT terminal should be
close to the power terminal
as much as possible.