netvox R718N360 User Manual page 7

Wireless 3-phase current meter interface
Hide thumbs Also See for R718N360:
Table of Contents

Advertisement

Example of ConfigureCmd
FPort:0x07
Bytes
1
CmdID
CmdID– 1 byte
DeviceType– 1 byte – Device Type of Device
NetvoxPayLoadData– var bytes (Max=9bytes)
Description
Device
Config
ReportReq
Config
ReportRsp
R718N360
ReadConfig
ReportReq
ReadConfig
ReportRsp
(1) Configure device parameters MinTime = 1min, MaxTime = 1min, CurrentChange = 100mA
Downlink: 01CA003C003C0000006400
The device returns:
81CA000000000000000000 (Configuration successful)
81CA010000000000000000 (Configuration fail)
(2) Read device configuration parameters
Downlink: 02CA000000000000000000
The device returns:
82CA003C003C0000006400 (current device parameters)
Example for MinTime/MaxTime logic:
Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime
Sleeping(MinTime)
Wakes up and collects data
REPORTS 3.6V
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange
value.
1
DeviceType
Cmd
Device
ID
Type
MinTime
0x01
(2bytes, Unit: s)
0x81
0xCA
0x02
MinTime
0x82
(2bytes, Unit: s)
Wakes up and collects data
REPORTS 3.6V
Var(Fix =9 Bytes)
NetvoxPayLoadData
NetvoxPayLoadData
MaxTime
(2bytes, Unit: s)
Status
(0x00_success)
Reserved (9Bytes, Fixed 0x00)
MaxTime
(2bytes, Unit: s)
MaxTime
Sleeping(MinTime)
Wake up and collects data
6
RawDataChange
(4bytes)
Reserved
(8Bytes, Fixed 0x00)
RawDataChange
(4bytes)
REPORTS 3.6V
Reserved
(1byte, Fixed 0x00)
Reserved
(1bytes, Fixed 0x00)