Daikin DSC Series Installation Instructions Manual page 20

Table of Contents

Advertisement

APPENDIX A BLOWER PERFORMANCE TABLES
EXTERNAL STATIC
SPEED
PRESSURE (ESP)
TAP
T1
T2
T3
T4
T5
NOTES:
Tables represent dry coil w ithout filter, to com pensate for filter add 0.08" to measured E.S.P. SCFM
correction for w et coil = 4 %.
5 Ton m odels are shipped from the factory w ith speed tap set on T4.
DIRECT DRIVE
DSH060 DOWNSHOT
DSH060****D DIRECT DRIVE DOWNSHOT
STANDARD
CFM
in w.c.
0.1
1205
0.2
1150
0.3
1065
0.4
980
0.5
860
0.6
800
0.1
1375
0.2
1300
0.3
1230
0.4
1180
0.5
1100
0.6
1005
0.7
970
0.8
915
0.9
845
0.1
1790
0.2
1745
0.3
1700
0.4
1650
0.5
1580
0.6
1515
0.7
1480
0.8
1420
0.9
1375
0.1
1920
0.2
1910
0.3
1850
0.4
1795
0.5
1760
0.6
1710
0.7
1640
0.8
1610
0.9
1560
0.1
2090
0.2
2040
0.3
1985
0.4
1935
0.5
1900
0.6
1855
0.7
1810
0.8
1750
0.9
1680
AMPS
1.47
1.54
1.59
1.68
1.79
1.82
1.94
2.01
2.05
2.15
2.22
2.33
2.43
2.51
2.57
3.37
3.40
3.49
3.56
3.63
3.71
3.75
3.84
3.85
4.48
4.57
4.66
4.78
4.84
4.96
5.06
5.19
5.22
5.35
5.38
5.70
5.44
5.82
5.73
5.69
5.82
5.94
20
WATTS
RPM
180
635
185
675
185
730
195
760
200
810
220
840
235
690
245
720
255
750
265
790
275
830
285
890
295
900
310
940
315
980
573
948
580
965
595
985
606
1007
616
1035
626
1059
648
1079
648
1100
652
1117
650
976
620
940
635
965
655
990
670
1020
685
1045
675
1065
690
1090
700
1125
720
970
740
990
755
1025
760
1035
780
1050
800
1075
810
1090
825
1120
840
1145

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dsh seriesDsc036Dsc048Dsc060Dsh036Dsh048 ... Show all