APPENDIX A BLOWER PERFORMANCE TABLES
STANDARD DSC060 DOWN SHOT
EXTERNAL STATIC
SPEED
PRESSURE (ESP)
TAP
T1
T2
T3
T4
T5
NOTES:
Tables represent dry coil w ithout filter, to com pensate for filter add 0.08" to m easured E.S.P. SCFM
correction for w et coil = 4 %.
5 Ton m odels are shipped from the factory w ith speed tap set on T4.
DIRECT DRIVE
DIRECT DRIVE DOWN SHOT
STANDARD
CFM
in w.c.
0.10
1205
0.20
1150
0.30
1065
0.40
980
0.50
860
0.60
800
0.10
1375
0.20
1300
0.30
1230
0.40
1180
0.50
1100
0.60
1005
0.70
970
0.80
915
0.90
845
0.10
1755
0.20
1700
0.30
1665
0.40
1580
0.50
1545
0.60
1505
0.70
1430
0.80
1370
0.90
1300
0.10
1945
0.20
1910
0.30
1850
0.40
1795
0.50
1760
0.60
1710
0.70
1640
0.80
1610
0.90
1560
0.10
2090
0.20
2040
0.30
1985
0.40
1935
0.50
1900
0.60
1855
0.70
1810
0.80
1750
0.90
1680
17
AMPS
WATTS
1.47
180
1.54
185
1.59
185
1.68
195
1.79
200
1.82
220
1.94
235
2.01
245
2.05
255
2.15
265
2.22
275
2.33
285
2.43
295
2.51
310
2.57
315
3.34
385
3.47
395
3.56
410
3.68
425
3.72
435
3.80
520
3.93
530
4.08
535
4.12
570
4.46
600
4.57
620
4.66
635
4.78
655
4.84
670
4.96
685
5.06
675
5.19
690
5.22
700
5.35
720
5.38
740
5.70
755
5.44
760
5.82
780
5.73
800
5.69
810
5.82
825
5.94
840
RPM
635
675
730
760
810
840
690
720
750
790
830
890
900
940
980
850
865
895
930
955
990
1020
1040
1070
920
940
965
990
1020
1045
1065
1090
1125
970
990
1025
1035
1050
1075
1090
1120
1145