APPENDIX A BLOWER PERFORMANCE TABLES
STANDARD DOWN SHOT AND HORIZONTAL
EXTERNAL STATIC
SPEED TAP
PRESSURE (ESP)
LOW
MED
HIGH
EXTERNAL STATIC
SPEED TAP
PRESSURE (ESP)
LOW
MED
HIGH
NOTES:
Tables represent dry coil w ithout filter, to com pensate for filter add 0.08" to m easured E.S.P. SCFM
correction for w et coil = 4 %.
4 Ton m odels are shipped from the factory w ith speed tap set on MED.
DIRECT DRIVE
DSC/DSH048 DIRECT DRIVE DOWN SHOT
STANDARD
CFM
in w.c.
0.10
1548
0.20
1500
0.30
1425
0.40
1353
0.50
1273
0.10
1660
0.20
1625
0.30
1565
0.40
1485
0.50
1405
0.60
1285
0.70
1200
0.10
1825
0.20
1745
0.30
1670
0.40
1585
0.50
1480
0.60
1405
DSC/DSH048 DIRECT DRIVE HORIZONTAL
STANDARD
CFM
in w.c.
0.10
1570
0.20
1520
0.30
1445
0.40
1375
0.50
1295
0.10
1715
0.20
1655
0.30
1580
0.40
1500
0.50
1405
0.60
1305
0.70
1200
0.10
1839
0.20
1770
0.30
1696
0.40
1611
0.50
1510
0.60
1418
AMPS
2.03
2.00
1.89
1.83
1.75
2.31
2.25
2.19
2.12
2.12
1.98
1.93
2.65
2.55
2.53
2.46
2.37
2.31
AMPS
2.09
2.06
1.95
1.89
1.81
2.39
2.32
2.24
2.16
2.09
2.00
1.92
2.77
2.70
2.62
2.53
2.44
2.36
16
WATTS
RPM
480
930
470
945
450
970
430
995
415
1020
540
1020
530
1035
515
1040
505
1050
500
1055
465
1060
440
1070
620
1045
600
1060
590
1065
575
1070
550
1080
535
1090
WATTS
RPM
490
905
480
920
460
945
440
970
425
995
560
975
545
985
525
1005
505
1020
490
1035
465
1050
440
1065
650
1030
630
1040
610
1050
590
1060
560
1070
540
1085