Optional Additional RS485 Connections

The additional (optional) RS485 communication port is located at the rear of the relay and can be connected
using a suitable RS485 120 ohm screened twisted pair cable.
The RS485 electrical connection can be used in a single or multi-drop configuration. When used with Reydisp the
RS485 master must support and use the Auto Device Enable (ADE) feature.
The last device in the connection must be terminated correctly in accordance with the master device driving the
connection. The relays are fitted with an internal terminating resistor which can be connected between the A and
B by fitting an external wire loop between terminals 18 and 20 on the power supply module.
6.5

Optional RS232 Connections

The additional (optional) RS232 (9 pin plug) (DTE) communication port is located at the rear of the relay and can
be connected using a suitable RS232 cable.
Where there is a requirement for multi-drop RS232 connection, a suitable device to facilitate this should be
obtained.
©2013 Siemens Protection Devices Limited
Pin
Relay Function
1
Not Connected
2
Receive Data (RXD)
3
Transmit Data (TXD)
4
Output Supply +5V 50mA
5
Signal Ground (GND)
6
Output Supply +5V 50mA
7
Linked to 8 (volts free)
8
Linked to 7 (volts free)
9
Output Supply +5V 50mA
Figure 6.5-1 RS232 Data Comms Pin Connections
Chapter 5) 7SR23 DAD Installation Guide