Section 4: Modbus Definitions

4.1

Introduction

This section describes the MODBUS-RTU protocol implementation in the relays. This protocol is used for
communication with a suitable control system.
This protocol can be set to use the Fibre Optic and RS485 ports. The relay can communicate simultaneously on
all ports regardless of protocol used.
Each relay must be given an address to enable communication and can be set by the Communication
Interface:Relay Address. Valid settings are within the range 1 – 247, a relay with the default address of 0 will not
be able to communicate.
Definitions with shaded area are not available on all relay models.
Table 5: Modbus-RTU Coils (Read/Write)
Address
00001
Binary Output 1
00002
Binary Output 2
00003
Binary Output 3
00004
Binary Output 4
00005
Binary Output 5
00006
Binary Output 6
00007
Binary Output 7
00008
Binary Output 8
00009
Binary Output 9
00010
Binary Output 10
00011
Binary Output 11
00012
Binary Output 12
00013
Binary Output 13
00014
Binary Output 14
00015
Binary Output 15
00016
Binary Output 16
00100
LED Reset
00101
Setting G1 selected
00102
Setting G2 selected
00103
Setting G3 selected
00104
Setting G4 selected
00105
Setting G5 selected
00106
Setting G6 selected
00107
Setting G7 selected
00108
Setting G8 selected
00120
Local mode
00121
Remote mode
00122
Service mode
00123
Local & Remote
00124
E/F Out
00130
Zone Switch Out
00131
Reset CB Trip Count
00132
Reset CB Delta Cnt
00133
Reset CB1 Open Cnt
00134
Reset CB1 Delta Cnt
00135
Reset CB2 Open Cnt
00136
Reset CB2 Delta Cnt
00137
Reset CB3 Open Cnt
©2013 Siemens Protection Devices Limited
Description
Chapter 4) 7SR23 DAD Data Communications
Write
Only
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Chapter 4 Page 23 of 54