Parameters
Code
Parameter
P3.13.9.2
Superv. Signal
P3.13.9.3
Superv. Unit Sel.
P3.13.9.4
Superv. Unit Decimal
P3.13.9.5
Superv. Unit Min
P3.13.9.6
Superv. Unit Max
P3.13.9.7
Superv. Alarm Level
P3.13.9.8
Superv. Fault Level
P3.13.9.9
Superv. Fault Delay
P3.13.9.10
PID setpoint Reduct.
V3.13.9.11
InputPress. Monitor
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Table 113. Input pressure supervision parameters
Min
Max
0
13
0
8
0
4
Varies
Varies
Varies
Varies
Varies
Varies
Varies
Varies
0.00
60.00
0.0
100.0
Varies
Varies
Unit
Default
ID
Hz
0
1686
Varies
2
1687
2
1688
Varies
Varies
1689 Unit min and max parameters are
Varies
Varies
1690
Varies
Varies
1691
Varies
Varies
1692
s
5.00
1693
%
10.0
1694
Varies
Varies
1695
vacon • 131
Description
The source of input pressure
measurement signal:
0=Analogue input 1
1=Analogue input 2
2=Analogue input 3
3=Analogue input 4
4=Analogue input 5
5=Analogue input 6
6=ProcessDataIn1 (0-100%)
7=ProcessDataIn2 (0-100%)
8=ProcessDataIn3 (0-100%)
9=ProcessDataIn4 (0-100%)
10=ProcessDataIn5 (0-100%)
11=ProcessDataIn6 (0-100%)
12=ProcessDataIn7 (0-100%)
13=ProcessDataIn8 (0-100%)
Select unit for supervision. The
supervision signal (P3.13.9.2) can
be scaled to process units on the
panel.
Choose how many decimals to
show.
the signal values corresponding
to e.g. 4mA and 20 mA respec-
tively (scaled linearly between
these).
Alarm (Fault ID 1363) will be
launched if supervision signal
stays below the alarm level lon-
ger than the time defined by
parameter P3.13.9.9.
Fault (Fault ID 1409) will be
launched if supervision signal
stays below the fault level longer
than the time defined by parame-
ter P3.13.9.9.
Input
Delay time to launch the
pressure supervision
alarm
fault
or
if the supervi-
sion signal stays below the
alarm/fault level longer than
defined by this parameter.
Defines the rate of the PID con-
troller setpoint reduction when
the Input pressure supervision
alarm is active.
Monitoring value for selected
Input pressure supervision sig-
nal.
Scaling value according to
P3.13.9.4.