Configuration and startup

WARNING
Failure to install covers and ground leads could result in serious injury or
death.
Install all protective equipment covers and safety ground leads after
installation.
3.1
Verify installation
Ensure the transmitter is installed correctly. Verify mechanical installation
and all electrical and pneumatic connections.
CAUTION
Damage can result from having a cold transmitter exposed to the process
gases.
Make sure that the transmitter is turned on and operating prior to firing
up the combustion process.
During outages, and whenever possible, leave all transmitters running to
prevent condensation and premature aging from thermal cycling.
3.1.1
Verify configuration - Fieldbus electronics
There is one switch on the microprocessor board which must be set for the
Rosemount OCX8800 with Fieldbus electronics
the sample line heater control circuit. This switch is accessible through holes
in the electronics box.
CAUTION
If defaults are changed under power, damage to the electronics may occur.
Remove power from the Rosemount OCX8800 before changing defaults.
Quick Start Guide
Quick Start Guide
(Figure
3-1). SW3 configures
31