Communication with the Host Using Memory Link

2-7-3 PC Switch Settings
2-8
Communication with the Host Using Memory Link
54
When the PC and NT620S/NT620C units have been connected, set the switches
at the CPU module at the PC side in order to enable communication using the NT
link method.
S C series, C200HX/HG/HE
Write the communication conditions directly to the "PC system area" (data
memory) using a peripheral tool (e.g., SYSMAC support software). For details
on the operation for setting the "PC system area", refer to the "SYSMAC
C200HX/HG/HE OPERATION MANUAL" (W303-E1-j).
[PC system setting area setting]
With C200HX/HG/HE, the setting area differs according to which port among the
standard port of the CPU module and the ports of the expansion communication
board is used for the connection.
Port
Channel #
C200HX/HG/HE
DM6645
RS-232C port
C200HX/HG/HE
DM6555
port A
C200HX/HG/HE
DM6550
port B
(*) When using C200HE, the PT unit No. range is 1 to 3.
Connect the NT620S/NT620C and host (personal computer, computer for FA
applications, etc.) using the memory link method.
In order to do this, the "memory link" system must be installed using the system
installer.
In addition, the communication conditions must be set. Select the communica-
tion conditions from the following in accordance with the host used (see page
75).
Item
Data bit length
Stop bit
Parity
Baud rate
Flow control
Response
Section
Writing Value
Use NT link (1:N)
Use NT link (1:N)
j = highest unit No. in the
5j00
maximum number of con
maximum number of con-
nectable PTs (1 to 7). (*)
Setting
7/8 bits
1/2 bits
None/even/odd
2400/4800/9600/19200 bps
None, RS/CS, XON/XOFF
No, Yes
2-8
Settings