Table 28. Effective occupancy output
nviOccManCmd
Occupied
Unoccupied
2
Bypass
Standby
Not valid
(a) Occupied bypass is initiated by either a communicated request (nviOccManCmd = bypass) or a local input (zone sensor timed override ON button).
(b) Whenever an update of nviOccManCmd is received indicating Bypass, the bypass timer is set to the nviBypassTime and the countdown starts.
(c) If nviOccManCmd and nviOccSensor are not valid, nviOccSchedule is occupied, the bypass timer is zero, and the binary input is occupancy. Then, the
occupancy binary input can switch the control between occupied and occupied standby.
CNT-SVX08F-EN
Occupancy Sensor
nviOccSchedule
Arbitration Result
Does not matter
Does not matter
Does not matter
Does not matter
Occupied
Does not matter
Unoccupied
Does not matter
Standby
Does not matter
Occupied
Not valid
Unoccupied
Does not matter
Does not matter
Occupied
Occupied
Unoccupied
Unoccupied
Does not matter
Standby
Does not matter
Occupied
Not valid
Unoccupied
Bypass Timer
nvoEffectOccup
Does not matter
Occupied
Zero
Unoccupied
Not zero
Bypass
(b)
Does not matter
Occupied
(b)
Zero
Unoccupied
(b)
Not zero
Bypass
(b)
Zero
Standby
(b)
Not zero
Bypass
(b)
Does not matter
Occupied
(b)
Zero
Unoccupied
(b)
Not zero
Bypass
Zero
Standby
Not zero
Bypass
Does not matter
Occupied
Zero
Standby
Not zero
Bypass
Zero
Unoccupied
Not zero
Bypass
Zero
Standby
Not zero
Bypass
Does not matter
Occupied
Zero
Unoccupied
Not zero
Bypass
Troubleshooting
(a)
(a)
(a)
(a)
(a)
(c)
(a)
(a)
(a)
(a)
55