Binary Output 1 and 2 Troubleshooting

Binary outputs 1 and 2 are TRIAC outputs. They can be used as two separate outputs (staged) or
can control a tri-state modulating actuator. If binary outputs 1 and 2 are always off, then begin with
the troubleshooting steps in
The troubleshooting steps assume that the outputs are always off, but the troubleshooting steps
are much the same if the outputs are misbehaving in other ways.
Table 23. Binary outputs 1 and 2 troubleshooting of external wiring
Step Number
Action
Perform the initial troubleshooting steps described in
Step 1
operation is okay.
Inspect the wiring. Is there a good connection between the wire and the terminal blocks? Look
Step 2
for shorts or opens. Pay particular attention to wire splices.
If binary outputs 1 and 2 are still always off, then follow additional troubleshooting steps to assess
the configuration and operation of the outputs. For tri-state modulating outputs, refer to
and for 2-stage outputs, refer to
Table 24. Binary outputs 1 and 2 troubleshooting of configuration and operation for tri-state modulating actuator
Step Number
Action
Connect the Rover service tool to the LonTalk communication link, start the Rover service tool,
and select the MP501 you are troubleshooting from the Active Group Tree. The device plug-in
Step 1
for the selected MP501 will appear with the Status screen displayed in the workspace.
Refer to the Rover Service Software Installation, Operation, and Programming Guide (EMTX-
SVX01).
Select the Configuration button to display the Device Configuration screen, then select the I/
O tab. Is staged or tri-state modulating selected?
If analog output is selected, binary outputs 1 and 2 are not used.
Step 2
If staged is selected, go to
If tri-state modulating is selected, continue with this table.
At the I/O tab of the Device Configuration screen, verify that the actuator drive time is not zero.
Step 3
The outputs will not drive the actuator if the drive time is 0.
At the Device Configuration screen, select the PID tab and verify the maximum output is not
Step 4
0%. If the minimum and maximum are set to 0%, the output will not change. Verify that the
gains are not 0. If all three gains are 0, the PID output will always be 0%.
Select the Close button to display the Status workspace. Look at the Unit tab. Is the MP501
in unoccupied mode if configured as SCC?
If configured as generic, the MP501 may be disabled. If the mode is unoccupied (SCC) or
Step 5
disabled (generic), the controller will drive the outputs to their disabled position, typically 0%.
The disabled position is set on the PID tab of the Device Configuration screen.
If the controller is unoccupied but you think it should be in a different state, see
Arbitration (Only SCC Mode)," p.
At the Unit tab in the Status workspace, check diagnostics.
In SCC mode, if you're not using the network space temperature input and the hardwired space
temperature input fails, the tri-state modulating output drives to its fail-safe position.
Step 6
Similarly, in generic mode, if you're not using the network input and the hardwired input
(temperature, flow, pressure, percent, ppm) fails, the tri-state modulating output drives to the
fail-safe position. The fail-safe position is set on the PID tab of the Device Configuration screen.
The controller will return to normal operation when the sensor is no longer failed.
Compare the input to the setpoint.
In SCC mode the controller may be calculating that no heating or cooling capacity is required
Step 7
at this time.
Similarly, in generic mode, the input may be near enough to setpoint that the end device should
be driven closed.
Check to see if either of the network variables nviCmdOverride or nviEmergOverride is keeping
the end device closed. These variables can override the outputs.
Step 8
To view nviCmdOverride and nviEmergOverride, refer to the Rover Service Software
Installation, Operation, and Programming Guide (EMTX-SVX01).
CNT-SVX08F-EN
Table
23. Perform the steps in the order they are listed.
Table 17, p. 47
Table 25, p.
Table 25, p.
52.
52.
and verify general board
52.
"Occupancy
Troubleshooting
Probable Cause
General board problem
Wiring problem
Table 24
Probable Cause
Output configuration
problem.
Output configuration
problem.
PID loop configuration
problem.
The MP501 is in
unoccupied mode (in
SCC applications) or
disabled mode (in
generic applications).
Sensor failure
diagnostic.
Capacity not required.
Override.