Occupancy Binary Input

The binary input on the controller is used as an occupancy input if configured as SCC. For stand-
alone controllers (any unit not receiving a communicated occupancy request, typically from a
building automation system), the occupancy binary input determines the occupancy of the unit
based on the hardwired signal. Normally, the signal is hardwired to a binary switch or time clock.
For controllers that receive a communicated occupancy request from a building automation
system, the hardwired occupancy binary input is used with a communicated occupancy request to
place the controller in either occupied mode or occupied standby mode.
If neither the hardwired binary input nor a communicated request is used to select the occupancy
mode, the controller defaults to occupied mode.
Table 27, p. 54
p. 55
Table 27. Occupancy sensor arbitration
nviOccSensor
Not valid
Not valid
Not valid
Occupied
Unoccupied
54
shows the occupancy result of the hardwired binary input to the MP501.
shows the occupancy result of the hardwired input, network inputs, or ON/CANCEL buttons.
Binary Input Configuration
Generic (not used)
Occupancy
Occupancy
Does not matter
Does not matter
Binary Input
Does not matter
Open
Closed
Does not matter
Does not matter
Table 28,
Result
Occupied
Occupied
Unoccupied
Occupied
Unoccupied
CNT-SVX08F-EN