8. Indoor Unit Electronic Control Valve Control

INDOOR UNIT
8-1. During Normal Control
(1)
During Cooling mode operation
Stop
Fan
Thermostat OFF
Cooling
Thermostat ON
*
The target value for SH control is 4 – 12°F for the temperature difference between E3 and E1,
depending on the operating conditions.
However, the SH target value may increase if the required level decreases. In this case, because the
electronic control valve position moves toward the closed side, you should not assume that there is
insufficient gas.
1
(2)
During Heating mode operation
2
Stop
Fan
Thermostat OFF
3
Heat
Thermostat ON
* The target value for SC control is 10 – 40°F for the temperature difference between the pressure
sensor temperature and E1, depending on the operating conditions.
4
5
6
Electronic control valve position (pulses)
Outdoor unit operating
20 pulses
20 pulses
20 pulses
55 – 480 pulses
Performs SH control
Electronic control valve position (pulses)
Outdoor unit operating
Control to prevent refrigerant
55 – 80 pulses
accumulation
Control to prevent refrigerant
55 – 80 pulses
accumulation
Control to prevent refrigerant
55 – 80 pulses
accumulation
55 – 480 pulses
Performs SC distribution control
1 - 12
Mini ECO-i SYSTEM
Control Functions
Outdoor unit stopped
20 pulses
20 pulses
20 pulses
Outdoor unit stopped
85 pulses
85 pulses
85 pulses