Power Supply Selection; Cable Connections - E2S BExBG10D-P Instruction Manual

Flameproof xenon beacons for use in flammable gas and dust atmospheres
Hide thumbs Also See for BExBG10D-P:

Advertisement

8) Power Supply Selection

It is important that a suitable power supply is used to run the
equipment. The power supply selected must have the
necessary capacity to provide the input current to all of the
units.
The following table shows the input current taken by the
various beacons and shows the maximum voltage at which
the beacons can be operated:
Nominal I/P
Model No.
Voltage
BExBG10DPDC012
12Vdc
BExBG10DPDC024
24Vdc
BExBG10DPDC048
48Vdc
BExBG10DPAC115
115V ac
BExBG10DPAC230
230Vac
BExBG15DPDC024
24Vdc
BExBG15DPDC248
48Vdc
BExBG15DPAC115
115V ac
BExBG15DPAC230
230Vac
The input current will vary according to the voltage input
level. The current levels shown above are for nominal input
voltage.
9) Selection of Cable, Cable Glands and
Blanking elements
When selecting the cable size, consideration must be given
to the input current that each unit draws (see table above),
the number of beacons on the line and the length of the cable
runs. The cable size selected must have the necessary
capacity to provide the input current to all of the beacons
connected to the line.
For ambient temperatures over +40ºC the cable entry
temperature may exceed +70ºC and therefore suitable heat
resisting cables and cable glands must be used, with a rated
service temperature of at least 110ºC
The BExBG10D-P and BExBG15D-P beacons have dual
cable gland entries which have an M20 x1.5. The dual cable
gland entries have an M20 x 1.5 entry thread. To maintain the
ingress protection rating and mode of protection, the cable
entries must be fitted with suitably rated ATEX / IECEx
certified cable glands and/or suitably rated ATEX / IECEx
certified blanking devices during installation according to EN /
IEC60079-14.
If a high IP (Ingress Protection) rating is required then a
suitable sealing washer must be fitted under the cable glands
or blanking plugs.
For use in explosive dust atmospheres, a minimum ingress
protection rating of IP6X must be maintained.
The BEx beacon range can be supplied with the following
types of adapters:
M20 to ½" NPT
M20 to ¾" NPT
M20 to M25
It is important to note that stopping plugs cannot be fitted
onto adapters, only directly onto the M20 entries.
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D210-00-211-IS
Input
Max. I/P
Current
Volts
1.45A
14V
660mA
28V
340mA
54V
250mA
126V
110mA
253V
860mA
28V
480mA
54V
360mA
126V
170mA
253V
Issue 3
20-04-2020
Any other adapters used must be suitably rated and ATEX /
IECEx certified adapters.
10) Earthing
Both AC and DC beacon units must be connected to an
earth. The units are provided with internal and external
earthing terminals which are both located on the terminal
chamber section of the unit.
Internal
Earthing
2-off M20
Cable
Entries
Fig 3. Internal View of Cover
When using the internal earth terminal ensure that the
stainless steel M4 flat washer is between the incoming earth
wire and the enclosure.
Internal earthing connections should be made to the Internal
Earth terminal in the base of the housing using a ring crimp
terminal to secure the earth conductor under the earth clamp.
The earth conductor should be at least equal in size and
rating to the incoming power conductors.
External earthing connections should be made to the M5
earth stud, using a ring crimp terminal to secure the earth
conductor to the earth stud. The external earth conductor
should be at least 4mm² in size.

11) Cable Connections

Electrical connections are to be made into the terminal blocks
on the PCBA located in the flameproof enclosure. See
section 7 of this manual for access to the flameproof
enclosure.
Wires having a cross sectional area between 0.5 mm² to
2.5mm² can be connected to each terminal way. If an input
and output wire is required the 2-off Live/Neutral or +/-
terminals can be used. If fitting 2-off wires to one terminal
way the sum of the 2-off wires must be a maximum cross
sectional area of 2.5mm². Strip wires to 8mm. Wires may also
be fitted using ferrules. Terminal screws need to be tightened
down with a tightening torque of 0.45 Nm / 5 Lb-in. When
connecting wires to the terminals great care should be taken
to dress the wires so that when the cover is inserted into the
chamber the wires do not exert excess pressure on the
terminal blocks. This is particularly important when using
cables with large cross sectional areas such as 2.5mm².
sales@e-2-s.com
www.e-2-s.com
Sheet 3 of 5
Internal
Bonding
Wire
Terminal
External Earthing
Tel: +44 (0)208 743 8880
Fax: +44 (0)208 740 4200