Universal process controllers and indicators, 1/8, 1/4 and 1/2 din (30 pages)
Summary of Contents for ABB CP420B
Page 1
CP420 Installation and Operation Manual English ABB, 1SBC159102M0202 2008-09...
Page 2
Document number: ABB, 1SBC159102M0202 Please read the entire installation manual prior to installing and using this equipment. Only qualified personnel may install, operate or repair this equipment. ABB is not responsible for modified, altered or renovated equipment. Because the equipment has a wide range of applications, users must acquire the appropriate knowledge to use the equipment properly in their specific applications.
Self Test ..................15 System Menu ................16 Bench and Function Tests ............17 Setting Communication Parameters ........... 17 Touch Screen Calibration............18 Downloading an Application ............. 18 Uploading an Application ............19 Copying an Application ............. 21 Passwords................... 22 ABB, 1SBC159102M0202...
– The supplier neither guarantees that the operator terminal is suitable for your particular application, nor assumes responsibility for your product design, in- stallation or operation. ABB, 1SBC159102M0202...
Page 6
Dismantling and Scrapping – The operator terminal or parts thereof shall be recycled according to local regulations. – The following components contain substances that might be hazardous to health and the environment: lithium battery, electrolytic capacitor and display. ABB, 1SBC159102M0202...
Installation Installation Package Contents The following parts are found in the box: – Operator terminal CP420 – 4 installation fasteners – Power connector (connected to the 24 V DC power input) – Installation and operation manual (1SBC159102M0202) ABB, 1SBC159102M0202...
20 - 90% RH non-condensed Vibration endurance 0.5 mm displacement, 10-55 Hz, 2 hours per X-, Y- and Z-axis directions Shock endurance 10 G, 11 ms 3 times in each direction of X-, Y- and Z-axes EN61000-6-4, EN61000-6-2 Cooling Natural cooling ABB, 1SBC159102M0202...
Product Specifications Description of Parts Front Fixture mounting holes Power lamp Communication lamps Display Back DIP switches (1-10) DC power input COM1: RS232/RS485 COM2: RS422/RS485 ABB, 1SBC159102M0202...
Product Specifications External and Cut-out Dimensions +0.5 Unit: mm 160.7 -0.1 160.4 CUTOUT DIMENSION 45.3 44.6 170.3 Mounting Procedure 1. Cut out the control front panel to match the dimensions (mm) below. ABB, 1SBC159102M0202...
3. The operator terminal is to be installed within the angle of 0 to 135 shown below. Grounding To make sure that the operator terminal works properly and to prevent it from radiating radio frequency noise, it must be connected to the earth ground. ABB, 1SBC159102M0202...
The power connector is already plugged into the power input of operator terminal when the package is first opened. ° Use copper conductors only, 60/75 Wire Gauge Stripped Type Torque (AWG) Length Solid 28-12 7-8 mm 4.5 lb-in Stranded 30-12 7-8 mm 4.5 lb-in DC 24V ABB, 1SBC159102M0202...
The default user level is set to 9 if the operator terminal requires no password to start its operation. Reserved SW10 COM2 Port For RS485, this switch has to be set ON. For RS422, this switch has to be set OFF. ABB, 1SBC159102M0202...
After downloading again, all items should pass the self-test. Note: When using the operator terminal for the first time, remember to reset the real time clock (RTC). ABB, 1SBC159102M0202...
+ and - to set the value of the field. Copy Copies application data to another CP420. Calibrates the touch panel and adjusts LCD contrast. See also section 6.5 Touch Screen Calibration. Runs the application. ABB, 1SBC159102M0202...
Remember to set dip switch SW5 = ON if parameters are set in the operator terminal. To set parameters in CP400Soft, select Application/Workstation Setup. Select the Connection tab to set communication parameters. Note: Remember to set dip switch SW5 = OFF if parameters are set in CP400Soft. ABB, 1SBC159102M0202...
To avoid an electrical shock, be sure to switch off the power before connecting the download cable to the operator terminal. Set the dip switch SW7 = ON. After the self-test, the system menu will be displayed on the screen and the operator terminal is ready to download the application. ABB, 1SBC159102M0202...
Make sure that the operator terminal and the PC are connected according to section 6.6 Downloading an Application. Set the dip switch SW7 = ON. After the self-test, the system menu will be displayed on the screen and the operator terminal is ready to upload the application. ABB, 1SBC159102M0202...
Page 20
*.V6F file. Thus a source file can serve the purposes of maintenance and modification. Note: When uploading for the first time, make sure to first run the application once, or else the upload function will not work. ABB, 1SBC159102M0202...
For information about setting a password, please see section Passwords. The following appears on the screens during the copying: Note: When copying for the first time, make sure to first run the application once, or else the copy function will not work. ABB, 1SBC159102M0202...
2. User level 1 has the highest privilege and User level 9 has the lowest. Note: Only users of User Level 1 has the right of access to the password table. ABB, 1SBC159102M0202...
Page 23
CP420 to another. Note that setting this password is different from the passwords set in Scenarios 1-3. To set this password, select Application/Workstation Setup in CP400Soft. Under the Password tab, the designer is able to set the password. ABB, 1SBC159102M0202...
Page 24
ABB FRANCE ABB STOTZ-KONTAKT GmbH Division Automation Products Po Box 10 16 80 Export Department 69006 Heidelberg 10 rue Ampère Germany 69685 Chassieu Tel. : +49 (0) 6221/701-1190 France Fax. : +49 (0) 6221/701-1333 Tel. : +33 (0) 4 72 22 17 22 Fax.