EBARA GS Series Operating Instructions, Installation & Maintenance Manual page 16

Hide thumbs Also See for GS Series:
Table of Contents

Advertisement

End Suction Centrifugal
Fault
Low flow rate continued
Water comes out initially
and then stops abruptly.
Power surge
The bearings are
overheating.
EBARA
PUMPS AMERICAS CORPORATION
www.pumpsebara.com
(t) 803.327.5005
Causes
- Leakage in the delivery pipe.
- Impeller worn.
- Significant head losses in the
system.
- Liquid temperature very high. The
liquid is volatile.
- Cavitation.
- The pump has not been primed.
- Air entering the system.
- Air bubbles in the suction pipes.
- The suction head is too high for
the pump.
- The voltage is low or the
imbalance between the phases is
high.
- The flow rate is too high or the
head is too low.
- Foreign bodies inside the pump.
- The mechanical seal was not
fitted correctly.
- Bearings damaged.
- Friction in the rotation areas. The
shaft is bent.
- The direction of rotation is not
correct.
- The density and/or viscosity level
of the liquid is high.
- Bearings damaged.
- In operation for a long time with
the valve closed or half-closed.
(f) 803.327.5097
GS Series
Measures to be taken
- Check and repair.
- Check the impeller.
- Review the project.
- Review the project.
- Seek expert advice.
- Prime the pump correctly.
- Check and repair the suction
pipe and shaft seal.
- Vent the pipes.
- Review the project.
- Check the power supply.
- Partially shut off the delivery valve.
- Remove foreign bodies.
- Fit it correctly.
- Replace the bearings.
- Repair in specialist workshop.
- Check and correct the
connection.
- Review the project.
- Replace the bearings.
- Avoid such a situation; close the
valve or stop the pump.
16
rev. 03/22