Reliable N252 EC Quick Start Manual

Reliable N252 EC Quick Start Manual

Sin ra0842 k25.2 (360 metric) pendent and recessed pendent extended coverage density area sprinkler

Advertisement

Quick Links

cULus Listed and FM Approved
for Storage and Non-storage
applications

Features

1. Provides maximum coverage areas up to 196
ft
(18.21 m
) per sprinkler and 14 ft. (4.27 m)
2
2
by 14 ft. (4.27 m) spacing.
2. cULus Listed for recessed installation in fin-
ished ceilings with
3. Available in brass, white polyester, black
polyester, and custom color polyester fin-
ishes.
4. Ordinary, 165 °F (74 °C), and Intermediate, 212
°F (100 °C) temperature ratings.
5. cULus Listed for unobstructed or noncom-
bustible obstructed construction.

Listings and Approvals

1. Listed by Underwriters' Laboratories Inc. and UL
certified for Canada (cULus).
2. FM Approved (Pendent only) as a K25.2 Extended
Coverage Quick-Response Pendent Storage and
Non-storage sprinkler.
3. Approved for use in New York City based on UL List-
ing per Local Law 33/2007 and MEA 258-93-E
UL Listing Categories
Sprinklers, Automatic & Open
Sprinklers for Storage Protection (Standard Response
Area/Density)
UL Guide Number
VNIV
US Pat. No. 7,624,812
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
/
" (13 mm) adjustment.
1
2
Model N252 EC (SIN RA0842)
K25.2 (360 metric) Pendent
and Recessed Pendent
Extended Coverage Density
Area Sprinkler
N252 EC Pendent
(cULus Listed and FM Approved)
N252 EC Recessed Pendent
(cULus Listed)

Product Description

The Models N252 EC Pendent and Recessed Pendent
Sprinklers are control mode, extended coverage sprinklers for
storage and non-storage density/area applications. This in-
cludes protection of the storage and display of Class I through
Class IV commodities, non-expanded Group A Plastics, and
non-expanded, exposed Group A Plastics in retail stores. The
Model N252 EC sprinklers offer maximum coverage areas up
to 14 ft by 14 ft (196 ft
), which is almost twice of that provided
2
by standard coverage sprinklers. This offers the advantage of
decreasing the number of required sprinklers, reducing labor
and material costs.

Operation

The Reliable Model N252 Extended Coverage Pendent
and Recessed Pendent Sprinklers utilize a levered fusible
alloy solder link. When the link reaches the rated tempera-
ture, the solder melts and the two link halves separate al-
lowing sprinkler to operate and water to flow.
Bulletin 008
. E
Rev

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the N252 EC and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Reliable N252 EC

  • Page 1 When the link reaches the rated tempera- ture, the solder melts and the two link halves separate al- lowing sprinkler to operate and water to flow. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523...
  • Page 2 Fig. 1 Model N252 EC Pendent Fig. 2 Model N252 EC Recessed Pendent with Model FP Escutcheon...
  • Page 3 Model FP escutcheons are the only recessed es- sprinklers must be installed with the Model N (Fig. 3) sprin- cutcheons Listed for use with Model N252 EC sprinklers. kler wrench. Usage of wrenches other than those speci- Use of any other recessed escutcheon will void all listings fied may damage these sprinklers.
  • Page 4 Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.

Table of Contents