cULus Listed and FM Approved
for Storage and Non-storage
applications
Features
1. Provides maximum coverage areas up to 196
ft
(18.21 m
) per sprinkler and 14 ft. (4.27 m)
2
2
by 14 ft. (4.27 m) spacing.
2. cULus Listed for recessed installation in fin-
ished ceilings with
3. Available in brass, white polyester, black
polyester, and custom color polyester fin-
ishes.
4. Ordinary, 165 °F (74 °C), and Intermediate, 212
°F (100 °C) temperature ratings.
5. cULus Listed for unobstructed or noncom-
bustible obstructed construction.
Listings and Approvals
1. Listed by Underwriters' Laboratories Inc. and UL
certified for Canada (cULus).
2. FM Approved (Pendent only) as a K25.2 Extended
Coverage Quick-Response Pendent Storage and
Non-storage sprinkler.
3. Approved for use in New York City based on UL List-
ing per Local Law 33/2007 and MEA 258-93-E
UL Listing Categories
Sprinklers, Automatic & Open
Sprinklers for Storage Protection (Standard Response
Area/Density)
UL Guide Number
VNIV
US Pat. No. 7,624,812
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
/
" (13 mm) adjustment.
1
2
Model N252 EC (SIN RA0842)
K25.2 (360 metric) Pendent
and Recessed Pendent
Extended Coverage Density
Area Sprinkler
N252 EC Pendent
(cULus Listed and FM Approved)
N252 EC Recessed Pendent
(cULus Listed)
Product Description
The Models N252 EC Pendent and Recessed Pendent
Sprinklers are control mode, extended coverage sprinklers for
storage and non-storage density/area applications. This in-
cludes protection of the storage and display of Class I through
Class IV commodities, non-expanded Group A Plastics, and
non-expanded, exposed Group A Plastics in retail stores. The
Model N252 EC sprinklers offer maximum coverage areas up
to 14 ft by 14 ft (196 ft
), which is almost twice of that provided
2
by standard coverage sprinklers. This offers the advantage of
decreasing the number of required sprinklers, reducing labor
and material costs.
Operation
The Reliable Model N252 Extended Coverage Pendent
and Recessed Pendent Sprinklers utilize a levered fusible
alloy solder link. When the link reaches the rated tempera-
ture, the solder melts and the two link halves separate al-
lowing sprinkler to operate and water to flow.