Reliable LT56 Series Manual

Reliable LT56 Series Manual

Special sprinklers
Hide thumbs Also See for LT56 Series:

Advertisement

Features
• 28 ft x 10 ft (8.5 m x 3 m) max. coverage area
• UL Listed for Light Hazard occupancies
• Increased spacing and reduced water demand
in corridors compared with traditional extended
coverage sprinklers
Product Description
Model LT56 series sprinklers are UL Listed Specific Application
sprinklers designed for installation in accordance with NFPA
13. The sprinklers produce a spray pattern that is specifically
designed to cover long narrow spaces, such as corridors and
hallways, with fewer sprinklers and less water demand compared
with traditional extended coverage sprinklers.
Model LT56 series sprinklers are quick-response sprinklers for
use in Light Hazard occupancies only. Model LT56 and Model
LT56-300 sprinklers have a glass bulb operating element.
Model LT56L, LT56L-300, and LT56C sprinklers have a fusible
link operating element. Model LT56, LT56-300, LT56L, and
LT56L-300 sprinklers are available with Model FV recessed
escutcheons, Model FP recessed escutcheons, or Model CCP
concealed cover plates. Model LT56C sprinklers require a Model
G5 flat concealed cover plate.
Model G5 Flat Cover Plate
Operating
Sprinkler Model
Element
LT56
Glass Bulb
LT56L
Fusible Link
LT56-300
Glass Bulb
LT56L-300
Fusible Link
LT56C
Fusible Link
Model CCP Cover Plate
Max. Working
Pressure
psi (bar)
250 (17.2)
250 (17.2)
Pendent, Recessed Pendent or
Conical Concealed Pendent
300 (21)
300 (21)
175 (12)
www.reliablesprinkler.com
Model LT56 Series Special Sprinklers
Designed specifically for corridors and hallway
Important! Reliable fire sprinklers must be handled, stored, and
installed in accordance with the guidelines in Caution Sheet 310
and this bulletin. Failure to follow these instructions may result in
unintended operation or nonoperation of the fire protection system.
Models LT56 & LT56-300
Model FV Escutcheon
Model LT56C Sprinkler
Styles
Flat Concealed
Bulletin 058 August 2024
K5.6 (80 Metric)
UL Listed
Models LT56L & LT56L-300
Model FP Escutcheon
Table A
Sprinkler
Coverage
Identification
Areas
Number (SIN)
Table B
RA5814
Table C
R5814
Table D
RA5914
Table E
R5914
Table F
RA5994

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LT56 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Reliable LT56 Series

  • Page 1 Product Description Model LT56 series sprinklers are UL Listed Specific Application sprinklers designed for installation in accordance with NFPA 13. The sprinklers produce a spray pattern that is specifically designed to cover long narrow spaces, such as corridors and Models LT56 &...
  • Page 2 Model LT56 Specific Application Sprinkler SIN RA5814 Technical Specifications Sprinkler Finishes Style: Pendent, Recessed Pendent, or (See Table H) Conical Concealed Threads: 1/2” NPT or ISO 7-1 R1/2 Sensitivity Nominal K-Factor: 5.6 (80 metric) Quick-response Max. Working Pressure: 250 psi (17.2 bar) Min.
  • Page 3 Model LT56L Specific Application Sprinkler SIN R5814 Technical Specifications Sprinkler Finishes Style: Pendent, Recessed Pendent, or (See Table H) Conical Concealed Threads: 1/2” NPT or ISO 7-1 R1/2 Sensitivity Nominal K-Factor: 5.6 (80 metric) Quick-response Max. Working Pressure: 250 psi (17.2 bar) Min.
  • Page 4 Model LT56-300 Specific Application Sprinkler SIN RA5914 Technical Specifications Sprinkler Finishes Style: Pendent, Recessed Pendent, or (See Table H) Conical Concealed Threads: 1/2” NPT or ISO 7-1 R1/2 Sensitivity Nominal K-Factor: 5.6 (80 metric) Quick-response Max. Working Pressure: 300 psi (21 bar) Min.
  • Page 5 Model LT56L-300 Specific Application Sprinkler SIN R5914 Technical Specifications Sprinkler Finishes Style: Pendent, Recessed Pendent, or (See Table H) Conical Concealed Threads: 1/2” NPT or ISO 7-1 R1/2 Sensitivity Nominal K-Factor: 5.6 (80 metric) Quick-response Max. Working Pressure: 300 psi (21 bar) Min.
  • Page 6 Model LT56C Specific Application Sprinkler SIN RA5994 Technical Specifications Sprinkler Finishes Style: Flat Cover Plate Concealed Pendent (See Table H) Threads: 1/2” NPT or ISO 7-1 R1/2 Nominal K-Factor: 5.6 (80 metric) Sensitivity Max. Working Pressure: 175 psi (12 bar) Quick-response Min.
  • Page 7 Recessed Escutcheon and Concealed Cover Plate Diagrams Figure 6 Model FP Escutcheon Model FV Escutcheon CCP Cover Plate Model G5 Cover Plate Bulletin 058 Page 7 of 10 August 2024 www.reliablesprinkler.com...
  • Page 8: Listings And Approvals

    The deflector is marked with “<-28 FT->” to indicate the layout of Model LT56 series sprinklers is illustrated in Figure 9. direction of the 28 ft. (8.5 m) coverage length. Model LT56 series sprinklers need not be installed with the frame arms or towers Listings and Approvals parallel to the sprinkler pipe.
  • Page 9 Coverage Area Figure 7 Adjacent Sprinklers Figure 8 Example Sprinkler Layout Figure 9 Bulletin 058 Page 9 of 10 August 2024 www.reliablesprinkler.com...
  • Page 10: Maintenance

    Please also refer to Technical Bulletin 203. Guarantee Maintenance Reliable Model LT56 series sprinklers should be inspected and For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms, the sprinkler system maintained in accordance with NFPA 25, as and conditions, visit www.reliablesprinkler.com.