6.2.3 General configuration
Select General configuration tab to configure the Modbus connection parameters and number of signals to
integrate.
-
Number of signals. Define number of Modbus signals to integrate. Once defined, it will create all
communication objects required on the ETS Project.
-
Read on init delay. Time after initialization process to start uploading of all values in KNX network.
-
Modbus connection parameters.
o
Baudrate. Defines the communication speed for the RTU communication. Values from 2400 to
115200 bps.
o
Data Type. On the first field, it defines the number of bits used for data, on the second field it defines
the parity of the communication (None/Odd/Even), on the last field it defines the number of stop bits.
o
Interframe timeout. Minimum time between received frame and sent frame.
o
Deadband. Minimum COV (change of value) in a signal value to update it in the KNX system.
Once general configuration is finished, go to Table tab, to configure all Modbus registers.