Download Print this page

Introduction; Specification - Eaton ELC-COPBDP User Manual

Advertisement

1

Introduction

Profibus is an international, open and vendor- independent communication protocol widely
applied in manufacturing, production, processing and building automation and other automation
control fields. The Profibus system contains 3 types of protocols depending on different
application demands: Profibus-DP, Profibus-PA and Profibus-FMS.
The ELC-COPBDP provides the ability for an ELC processor to exchange data on a
Profibus-DP network. The ELC-COPBDP acts as a Profibus-DP slave to a Profibus-DP master
Features
Connects to any ELC processor
Allows for user selectable data contents (selected in the ELC program)
Cyclical data exchange process
Support the SYNC and FREEZE for data synchronization between master and slaves
Support Auto Baud rate detection
Support 12MHz baud rate
Cyclical data size is fixed to 4bytes input and 4bytes output
Provides GSD file for configuration using 3
2

Specification

Profibus-DP physical and transport layer
Interface
Transfer method
Transfer cable
Electrical isolation
Message types
Device ID
GSD file
Model Name
Baud rates
(Auto detected)
Environmental specifications and agency certifications
Noise Immunity
Operation/storage
temperature
2
For more Information visit: www.eaton.com
DB9 9 pin connector
High speed RS485
2-wire twisted shielded cable
500VDC
DPV0, Cyclical data exchange process
09B9 HEX
EATN09B9.GSD
ELC-COPBDP
9.6kbps, 19.2kbps, 93.75kbps, 187.5kbps, 500kbps, 1.5M bps, 3M
bps, 6M bps, 12M bps
ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O:
1KV, Analog & Communication I/O: 1KV
RS(IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m
Operation: 0°C ~55°C (Temperature), 50~95% (Humidity),
Pollution degree 2;
Storage: -25°C ~70°C (Temperature), 5~95% (Humidity)
ELC-COPBDP