ELC-AN04ANNN
Instruction Sheet
Analog to Digital Converter Module
WARNING
•
This Instruction Sheet only provides descriptions for electrical specifications, general
specifications, installation & wiring, troubleshooting and peripherals. For more information about
the optional peripherals, please see ELC Application Manual.
•
This is an OPEN TYPE Controller. The ELC should be kept in an enclosure away from airborne
dust, humidity, electric shock risk and vibration. Also, it is equipped with protective methods
such as some special tools or keys to open the enclosure, so as to avoid the hazard to users
and the damage to the ELC. Do NOT touch terminals when power on.
•
Never connect the AC main circuit power supply to any of the input/output terminals, as it will
damage the ELC. Check all the wiring prior to power up. To avoid any electromagnetic noise,
make sure the ELC is properly grounded
.
•
Warning – Do not disconnect while circuit is live unless area is known to be non-hazardous.
•
Power, input and output (I/O) wiring must be in accordance with Class 1, Div. 2 wiring methods -
Article 501-10(B)(1) of the National Electrical Code.
•
Suitable for use in Class 1, Division 2, Groups A, B, C, D or Non-Hazardous locations only.
•
Warning – Explosion hazard - Substitution of components may impair suitability for Class 1,
Division 2.
•
Warning – Explosion Hazard - Do not disconnect equipment unless power has been switched
off or the area is known to be Non-Hazardous.
1
INTRODUCTION
1.1 Model Explanation and Peripherals
Thank you for choosing Eaton Logic Controller (ELC) series products. The analog input module
receives external 4-point analog signal input (voltage or current) and transforms it into 14 bits digital
signal. The analog input module of ELC-AN04ANNN can read/write the data of analog input module
by using commands FROM / TO via ELC program. There are 49 CR (Control Register) in each
module and there are 16 bits in each register.
1.2 Product Profile and Outline
25.2
60
4
3
C
H
1
M
8
1
C
H
2
M
EXTENSION
C
PORT
H
M
3
9
10
C
H
2
4
M
7
3
6
8
5
Units: mm
1. Status indicator (Power, RUN and ERROR)
2. Model Name
3. Extension unit clip
4. Input/output terminal
5. DIN rail clip
6. Mounting hole of the extension unit
7. Nameplate
8. Extension unit clip
9. DIN rail (35mm)
10. Extension port
11. RS-485 Communication port
12. 2 pin removable terminal (standard accessory)
13. DC power input
14. Power input cable (standard accessory)
2007-05-08
1.3 External wiring
Voltage Input
-10V ~ +10V
CH1
*
5
5011629803-AN03
@
Isolation Wire
1¡@
*
Current Input
CH4
-20mA ~ +20mA
2
*
@
Isolation Wire
1¡@
*
*
3
@
terminal of
power module
*
4
@
System
Grounding
Class 3 Grounding
(100
Ω
or less)
Warning: DO NOT wire to the No function terminal. Use
Copper Conductor Only, 60/75 °C.
1.4 Terminal of analog module layout
AN04ANNN
AN02NANN
V+
V+
I+
I+
CO M
CO M
FG
FG
V+
V+
I+
I+
CO M
CO M
FG
FG
●
●
V+
I+
CO M
FG
V+
I+
CO M
FG
●
2
2.1 Function Specifications
FOUR CH. A/D MODULE
Power supply voltage
Analog input channel
Analog input range
Digital conversion range
Resolution
Input impedance
Overall accuracy
Response time
Isolation method
Isolation
11
Absolute input range
12
Digital data format
Average function
13
Self diagnose function
14
Communication mode (RS-485)
Connect to ELC in series
Max. rated consuming power
Noise Immunity
Note 1: Please isolate analog input and
other power wiring.
104.7K
CH1
V+
Note 2: If connect to current signal,
250 Ω
I+
104.7K
please short circuit between V+ and I+
COM
FG
terminals.
AG
~ ~
Note 3: If noise is too loud, please
104.7K
CH4
V+
connect FG to grounding.
250 Ω
I+
104.7K
COM
Note 4: Please connect
terminal
FG
AG
of power module and
terminal of
analog input module to system earth
+15V
DC/DC
24+
point and make system earth point be
AG
24-
Converter
-15V
grounding or connects to machine
cover.
Note 5: If wave of input terminal of
loaded is too big that noise interferes
wiring, please connect capacitance with
0.1~0.47uf 25V.
AN04NANN
AN06AANN
PT04ANNN
TC04ANNN
POWER
V+
POW ER
V+
L +
L +
ERROR
I+
ER ROR
I+
L -
L -
D/A
COM
A
D
CO M
I-
SLD
FG
V+
FG
●
V+
I+
L +
L +
I+
CO M
L -
L -
COM
V+
I-
SLD
FG
I+
FG
●
●
CO M
●
●
V+
V+
L +
L +
I+
I+
L -
L -
COM
CO M
I-
SLD
FG
V+
FG
V+
●
I+
L +
L +
I+
CO M
L -
L -
COM
V+
I-
SLD
FG
I+
FG
●
●
CO M
●
●
STANDARD SPECIFICATIONS
VOLTAGE INPUT
CURRENT INPUT
24 VDC(20.4VDC~28.8VDC) (-15%~+20%)
4 channel / each module
±20 mA
±10V
±8,000
±4,000
14 bits(1
=1.25 mV)
13 bits (1
=5μA)
LSB
LSB
200 KΩ and above
250Ω
±0.5% of full scale at 25℃(77℉)
±1% of full scale during 0~55℃ (32~131℉)
3 ms × channels
It has isolation between digital area and analog area. There is no isolation
among channels.
Field to Digital Area: 500V
Field to Analog Area: 500V
Analog area to Digital Area: 500V
Field to 24VDC: 500V
±15 V
±32 mA
2's complementary of 16-bit, 13 Significant Bits
Yes (CR#2~CR#5 can be set and setting range is K1~K100)
Upper and lower bound detection / channels
MODBUS ASCII/RTU Mode. Communication baud rate of 4,800 / 9,600 /
19,200 / 38,400 / 57,600 / 115,200 bps. For ASCII mode, date format is
7Bits, even, 1 stop bit (7,E,1). For RTU mode, date format is 8Bits, even, 1
stop bit (8,E,1). The RS-485 is disabled when the ELC-AN04ANNN is
connected in series to an ELC.
The input point of the first analog extension unit it connects from the near to
the distant is from 0 to 7. The Max. is 8 modules and it won't waste digital
I/O point.
24 VDC(20.4VDC~28.8VDC) ( –15%~+20%), 2W, supply from external
power
ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Analog & Communication I/O: 1KV
RS(IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m
The diameter of the grounding wire cannot be smaller than that of terminals
Grounding
24V and 0V (if numerous ELCs are used at the same time, make sure that
each ELC is grounded respectively to the ground poles)
International Standard Regulations: IEC61131-2, IEC 68-2-6 (TEST Fc)/
Vibration/Shock Immunity
IEC61131-2 & IEC 68-2-27 (TEST Ea)
Operation: 0℃~55℃(temperature), 50~95% (humidity), pollution degree: 2;
Operation/Storage Environment
Storage: -25℃~70℃(temperature), 5~95% (humidity)
UL508
UL1604, Class1,Div2 Operating temperature code: T5
Agency Approvals
European community EMC Directive 89/336/EEC and Low Voltage
Directive 73/23/EEC
3
CR (CONTROL REGISTER)
ELC-AN04ANNN
EXPLANATION
CR
Comm.
Latched
Register name
b15 b14 b13 b12 b11 b10 b9 b8 b7
No.
address
System used, data length is 8bits (b7~b0).
#0 H 4000 O
R
Model type
ELC-AN04ANNN model code =H 88
Reserved
CH4
Input mode setting: factory setting is H0000.
Mode 0: input voltage mode (-10V~+10V).
#1 H 4001 O R/W Input mode setting
Mode 1: input voltage mode (-6V~+10V).
Mode 2: input current mode (-12mA~+20mA)
Mode 3: input current mode(-20mA~+20mA)
Mode 4: Reserved.
#2 H 4002 O R/W CH1 average number
#3 H 4003 O R/W CH2 average number
Average numbers setting of channel CH1~CH4. Setting range is K1~K100
#4 H 4004 O R/W CH3 average number
and factory setting is K10.
#5 H 4005 O R/W CH4 average number
Average value of CH1 input
#6 H 4006 X
R
signal
Average value of CH2 input
#7 H 4007 X
R
signal
Display average value of CH1~CH4 input signal
Average value of CH3 input
#8 H 4008 X
R
signal
Average value of CH4 input
#9 H 4009 X
R
signal
#10 ~ #11
Reserved
Present value of CH1 input
#12 H 400C X
R
Display present value of CH1~CH4 input signal
signal
Present value of CH3 input
#14 H 400E X
R
signal
Display present value of CH1~CH4 input signal
Present value of CH4 input
#15 H 400F X
R
signal
#16 ~ #17
Reserved
To adjust OFFSET value of
#18 H 4012 O R/W
CH1
To adjust OFFSET value of
#19 H 4013 O R/W
Offset setting of CH1~CH4. Factory setting is K0 and unit is LSB.
CH2
Voltage input: setting range is K-4,000 ~K4,000
To adjust OFFSET value of
Current input: setting range is K-4,000 ~K4,000
#20 H 4014 O R/W
CH3
To adjust OFFSET value of
#21 H 4015 O R/W
CH4
#22 ~ #23
Reserved
#24 H 4018 O R/W To adjust GAIN value of CH1
GAIN setting of CH1~CH4. Factory setting is K4,000 and unit is LSB.
#25 H 4019 O R/W To adjust GAIN value of CH2
Voltage input: setting range is K-3,200 ~K16,000.
#26 H 401A O R/W To adjust GAIN value of CH3
Current input: setting range is K-3,200 ~K10,400.
#27 H 401B O R/W To adjust GAIN value of CH4
#28 ~ #29
Reserved
It is the data register to save all error status. Please refer to fault code chart
#30 H 401E X
R
Error status
for detail.
Communication address
Setting RS-485 communication address. Setting range is 01~255 and
#31 H 401F O R/W
setting
factory setting is K1
It is used to set communication baud rate (4,800, 9,600, 19,200, 38,400,
57,600, 115,200bps). Communication format: ASCII mode is 7Bit, even bit, 1
stop bit (7,E,1). Communication format of RTU mode is 8Bit, even bit, 1 stop
bit (8,E,1).
Communication baud rate
b0: 4,800 bps (bit/sec).
#32 H 4020 O R/W
setting
b2: 19,200 bps (bit/sec).
b4: 57,600 bps (bit/sec).
b6~b13: reserved.
b14: exchange low and high byte of CRC check code (only for RTU mode)
b15: ASCII / RTU mode selection
b15 b14 B13 b12 b11 b10 b9 b8 b7
Reserved
CH4
Output latched setting, factory setting H0000
Give CH1 setting for example:
Reset to factory setting and set
1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#18,
#33 H 4021 O R/W
characteristics adjustable
CR#24). When b0=1, inhibit user to adjust OFFSET and GAIN value of
priority
CH1 (CR#18, CR#24).
2. b1 means if characteristic register is latched. b1=0 (factory setting,
latched), b1=1 (not latched).
3. When b2 is set to 1, all settings will reset to factory setting.
IL05003002E.pdf
b6
b5 b4
b3
b2 b1 b0
CH3
CH2
CH1
b1: 9,600 bps (bit/sec). (factory setting)
b3: 38,400 bps (bit/sec).
b5: 115,200 bps (bit/sec).
b6
b5 b4
b3
b2 b1 b0
CH3
CH2
CH1