Menu 5 - Service - Nibe SMO 20 Installer Manual

Hide thumbs Also See for SMO 20:
Table of Contents

Advertisement

Menu 5 - SERVICE

OVERVIEW
5 - SERVICE
5.1 - operating settings
5.2 - system settings
5.4 - soft in/outputs
5.5 - factory setting service
5.6 - forced control
5.7 - start guide
5.8 - quick start
5.9 - floor drying function
5.10 - change log
5.11 - heat pump settings
5.12 - country
* Accessory needed.
Go to the main menu and hold the Back button in for 7
seconds to access the Service menu.
Sub-menus
Menu
SERVICE
has orange text and is intended for the ad-
vanced user. This menu has several sub-menus. Status in-
formation for the relevant menu can be found on the display
to the right of the menus.
operating settings
Operating settings for the control
module.
system settings
System settings for the control module,
activating accessories etc.
soft in/outputs
Setting software-controlled inputs and
outputs on terminal block (X2).
factory setting service
Total reset of all settings (including
settings available to the user ) to default values.
forced control
Forced control of the different components
in the indoor module.
start guide
Manual start of the start guide which is run the
first time when the control module is started.
quick start
Quick starting the compressor.
NOTE
Incorrect settings in the service menus can dam-
age the installation.
MENU 5.1 - OPERATING SETTINGS
Operating settings can be made for the control module in
the sub menus.
NIBE SMO 20
5.1.1 - hot water settings *
5.1.2 - max flow line temperature
5.1.3 - max diff flow line temp.
5.1.4 - alarm actions
5.1.12 - addition
5.1.14 - flow set. climate system
5.1.22 - heat pump testing
5.1.23 - compressor curve
5.2.2 - installed heat pump
5.2.4 - accessories
MENU 5.1.1 - HOT WATER SETTINGS
The hot water settings require that hot water production is
activated in menu 5.2.4 accessories.
economy
Setting range start temp. economy: 5 – 55 °C
Factory setting start temp. economy: 42 °C
Setting range stop temp. economy: 5 – 60 °C
Factory setting stop temp. economy: 48 °C
normal
Setting range start temp. normal: 5 – 60 °C
Factory setting start temp. normal: 46 °C
Setting range stop temp. normal: 5 – 65 °C
Factory setting stop temp. normal: 50 °C
luxury
Setting range start temp. lux: 5 – 70 °C
Factory setting start temp. lux: 49 °C
Setting range stop temp. lux: 5 – 70 °C
Factory setting stop temp. lux: 53 °C
stop temp. per. increase
Setting range: 55 – 70 °C
Factory setting: 55 °C
charge method
Setting range: target temp, delta temp
Default value: delta temp
5.11.1.1 - heat pump
5.11.1.2 - charge pump (GP12)
Chapter 8 | Control
37

Advertisement

Table of Contents
loading

Table of Contents