Advertisement

Menu 5 - SERVICE

5 - SERVICE
Hold the back button in for 7 seconds to access the Ser-
vice menu.
Sub-menus
Menu
SERVICE
advanced user. This menu has several sub-menus. Status
information for the relevant menu can be found on the
display to the right of the menus.
operating settings
system settings
tivating accessories etc.
factory setting service
settings available to the user ) to default values.
NOTE
Incorrect settings in the service menus can
damage the heat pump.
Menu 5.1 - operating settings
Operating settings can be made for the heat pump in the
sub menus.
28
Chapter 8 |
Control - Menus
5.1 - operating settings
5.2 - system settings
5.5 - factory setting service
has orange text and is intended for the
Operating settings for the heat pump.
System settings for the heat pump, ac-
Total reset of all settings (including
Overview
5.1.1 - hot water settings
5.1.2 - max flow line temperature
5.1.4 - alarm actions
Menu 5.1.1 - hot water settings
economy
Setting range start temp. economy: 5– 70 °C
Factory setting start temp. economy: 41 °C
Setting range stop temp. economy: 5– 70 °C
Factory setting stop temp. economy: 45 °C
normal
Setting range start temp. normal: 5– 70 °C
Factory setting start temp. normal: 43 °C
Setting range stop temp. normal: 5– 70 °C
Factory setting stop temp. normal: 47 °C
luxury
Setting range start temp. lux: 5– 70 °C
Factory setting start temp. lux: 45 °C
Setting range stop temp. lux: 5– 70 °C
Factory setting stop temp. lux: 49 °C
stop temp. per. increase
Setting range: 55 – 70 °C
Default values: 55 °C
Recommended normal setting
Heat pump
Water heater
F2026
F2026
F2300
F2300
Here you set the start and stop temperature of the hot
water for the different comfort options in menu 2.2 as
well as the stop temperature for periodic increase in menu
2.9.1.
The above values are the default settings when there are
different heater designs, sensor locations and other
factors that are unique to each installation. These settings
may therefore need adjusting.
Start
Stop
VPA
43 °C
47 °C
VPB
42 °C
46 °C
VPA
48 °C
52 °C
VPB
46 °C
50 °C
SMO 05