Min (Overlap Compensation); Max (Output Scaling); Trigger (Threshold Value Of Min Function) - WEST PAM-199-P-PDP Technical Documentation Manual

Universal power amplifier with profibusdp interface
Table of Contents

Advertisement

5.5.2 MIN (Overlap compensation)

5.5.3 MAX (Output scaling)

5.5.4 TRIGGER (Threshold value of MIN function)

Command
MIN:I
MAX:I
TRIGGER
The output signal is adapted to the valve by these commands. With the MAX value the output signal (the maxi-
mum valve current) will be defined. With the MIN value the overlap (dead band of the valve) will be compen-
sated. Via the TRIGGER the activation point of the MIN function is set and so a non-sensitive range around
1
the zero-point
can be specified.
CAUTION: If the MIN value is set too high, it influences the minimal velocity, which cannot be
adjusted any longer.
MIN:B
MAX:B
Fig.1: mode 195, directional valve with 2 solenoids
1
This dead band is necessary, in order to avoid unrequested activations caused by small variations of the input signal. If
this module is used in a position controls, the TRIGGER value should be reduced (typical: 1...10).
Page 24 of 37
Parameters
i= A|B
X
x= 0... 6000
X
x= 5000... 10000
X
x= 0... 3000
Input
TRIGGER
PAM-199-P-PDP
Unit
-
0.01%
0.01%
0.01%
MAX:A
10V
MIN:A
TRIGGER
fig.2: mode 196, one solenoid each channel
Group
STD
100%
Eingang / Input
05.06.2020
MAX
MIN