WEST PAM-199-P-PDP Technical Documentation Manual page 23

Universal power amplifier with profibusdp interface
Table of Contents

Advertisement

5.5.1.2 Mode 196, one solenoid each
In case of using single solenoid valves, only the first quadrant is active. The curve is calculated according to
the equation of the linear interpolation y=(x-x1)*(y1-y0)/(x1-x0)+y1.
The influence of the linearization can be estimated via the process data on the monitor or on the oscilloscope.
For the input of the characteristics linearization, the WPC-300 program provides a table and a graphic data
input. The input signal is mapped on to the X-axis and the output signal is mapped on to the Y-axis.
Page 23 of 37
PAM-199-P-PDP
05.06.2020