The qualified personnel have skills and experience in dealing with electrical (open-loop) control technology. Additional information – Contact the regional Festo contact if you have technical problems è www.festo.com. – Accessories and spare parts è www.festo.com/catalogue. Festo — VABA-S6-1-AP — 2022-06...
VTSA-F-MP(-NPT) and the automation system CPX-AP-I. Mounting Depending on the configuration, the electrical interface VABA-S6-1-AP is already integrated in the valve terminal. The product is also suitable for retrofit in existing valve terminals with multi-pin connection type VTSA-MP (-NPT) and VTSA-F-MP (-NPT).
M8 socket, 4-pin, A-coded Signal +24 V DC logic supply PS 0 V DC load supply PL 0 V DC logic supply PS +24 V DC load supply PL Tab. 3: Connection for voltage forwarding Festo — VABA-S6-1-AP — 2022-06...
Tab. 6: Response of the LED displays of the module after error-free commissioning Information on troubleshooting in the event of incorrect response: • è 1 Applicable documents,Operating instructions automation system CPX-AP-I. • è 9 Malfunctions Festo — VABA-S6-1-AP — 2022-06...
Fig. 2: Example of address assignment with 12 valve positions Parameterisation Various parameters are available for reading out information about the modules in an automation system CPX-AP and adapting the modules to the application situation. Festo — VABA-S6-1-AP — 2022-06...
All diagnostic messages of the automation system and also information on the grouping and display of the diagnostic messages è 1 Applicable documents, Operating instructions automation system CPX-AP-I. The table below contains the diagnostic messages of the module. Festo — VABA-S6-1-AP — 2022-06...
Page 10
02 | 01 | 013F Overvoltage in load Overvoltage in load supply (PL) 24 V DC (33620287) supply (PL) 24 V DC – Check power supply Remedy Diagnos- Error tics status Tab. 9: Diagnostic messages Festo — VABA-S6-1-AP — 2022-06...
PL red light Module ramp-up not yet completed. – System communication not yet initial- ised. fast red flashing Module identification (service function) – fast green flashing Tab. 10: LED module diagnostics [MD] Festo — VABA-S6-1-AP — 2022-06...
0 V PL to FE [nF] Typically 20 Electrical isolation Between PS and PL Between the channels Short-circuit protection Per channel Electronic Response after end of No automatic recovery the overload Tab. 14: Power supply Festo — VABA-S6-1-AP — 2022-06...