Notes on the Multi-MPP Tracker inverter

Multi MPP Track-
er – Inverter
DC-1
Connecting two solar module fields to a Multi MPP
Tracker inverter
Connecting multiple combined solar module fields to a
line on a Multi MPP Tracker inverter
PV 1
PV 1
PV 2
max 33 A to a single
DC terminal
DC-2
DC+1
DC+2
+
+
1
2
DC
DC
DC
DC
+1
+1
+2
+2
1
2
3 1 2 3
PV 1
PV 2
M P P T R A C K E R 2
O F F
10.0-3, 12.0-3 max. 43,5A
15.0-3,17.5-3,20.0-3 max 51A
DC+
DC-1
42,0201,4479 42,0201,4480
DC+1
42,0201,4479
Multi MPP Tracker inverters have two inde-
pendent DC inputs (MPP Tracker). These
inputs can be connected to a number of dif-
ferent modules.
Each MPP Tracker has 3 DC+ terminals.
There are a total of six DC- terminals.
Connecting two–six strings in Multi MPP
Tracker mode:
Connect the strings separately to the two
DC
DC
-
MPP Tracker inputs (DC+1/DC+2). The
1 2 3 4 5 6
DC- terminals can be used as desired, sin-
ce they are connected internally.
Set MPP TRACKER 2 to "ON" when star-
ting for the first time (also subsequently
possible in the basic menu)
Single MPP Tracker mode on a Multi MPP
Tracker inverter:
B A S I C
If the inverter is being operated with an ex-
ternal string collection box, the DC connec-
tor kit (item numbers 42,0201,4479 and
42,0201,4480) must be used
DC-
Set MPP TRACKER 2 to "OFF" when star-
ting for the first time (also subsequently
42,0201,4480
possible in the basic menu)
If the Multi MPP Tracker inverter is opera-
ted in Single MPP Tracker mode, the cur-
rents of the connected DC lines are
distributed evenly across both inputs.