Summary of Contents for asecos ION-STORE-90
Page 1
Safety storage cabinets for storage of lithium ion batteries 10 YEARS WARRANTY Upon conclusion of an asecos service and maintenance agreement (PREMIUM tari ), you will get a warranty extension for up to 10 years for your ION-LINE safety storage cabinet.
Page 3
YOUR PERSONAL DOCUMENTATION TO THE asecos SAFETY CABINET Dear Customer, you have made a decisive investment in safety for your company by purchasing this asecos safety storage cabinet. You now own an innovative product made of top-quality materials guaranteeing the highest quality standards.
The guarantee for this product is agreed between you (the customer) and your dealer (the seller). As the manufacturer, asecos guarantees the products listed in the operating instructions for a period of 24 months from the date of delivery. All model safety equipment are subject to a compulsory annual inspection by spe- cialised sta authorised by the manufacturer.
2. TRANSPORT CAUTION: Transport the cabinet in an upright position on a pallet truck, tied and secured against slipping, until the fi nal place of installation is reached.The transport locks in the door joints may only be removed directly at the place of installation! Inappropriate transport can lead to concealed damage to the fi re protection insulation! We can only guarantee the necessary quality if the cabinet is transported to the place of its use by our specially trained sta .
2.3. IN PLANT TRANSPORT • In-plant transport is also possible without transport locks (inserted as standard in the door joints) ATTENTION: The doors must be locked prior to transport! The optional extraction unit is inside the cabinet and is only mounted after the in-plant transport to the place of use.
3. INSTALLATION 3.1. ALIGNMENT OF THE CABINETS CAUTION: Door elements must not scrape against the fi re prevention seals in the fold of the door when opening and closing! Doors with an automatic closing mechanism must close automatically from every position and the lock must be able to lock! 4×...
5. INTERIOR FITTINGS 5.1. BOTTOM COLLECTING SUMP According to EN 14470-1: The bottom collecting sump must be able to hold a minimum volume of 10 %of all the containers stored in the cabinet [1] or at least 110 %of the volume of the largest single container [2] , whichever of these volumes is larger.
5.3. SHELVES HEIGHT ADJUSTABLE IO90.195.060.K1.WDC IO90.195.120.K1.WDC / IO90.195.120.K2.WDC* Load capacity (kg/drum platform) Gilt bei Special interior equipment: Order No. 38516 / 38517 Order No. 38518 / 38519 max. 25 kg max. 75 kg max. 50 kg ATTENTION: Model IO90.195.120.K2.WDC: The position of the fi re suppression device, smoke detector, thermal sensor must not be changed when adjusting the height of the shelves.
fi re protection and CE conformity are maintained. For this purpose, the cabinet must be handed over to the main factory of asecos GmbH in Gründau, where the specialist department - depending on the degree of damage - makes an assessment of the economic e ciency and technical possibilities of a repair.
This annual check can be carried out with the necessary care, and for securing your warranty claims in the case of fi re, only by an authorised asecos employ- ee (refer also to our service brochure regarding this).
10. TECHNICAL DRAWING Top view Top view Top view (155) (155) (155) Exhaust air DN 75 Exhaust air DN 75 Fresh air Fresh air Fresh air Exhaust air DN 75 1017 1017 IO90.195.120.K1.WDC IO90.195.060.K1.WDC IO90.195.120.K2.WDC 11. TECHNICAL DATA IO90.195.120.K1.WDC IO90.195.060.K1.WDC IO90.195.120.K2.WDC Type External dimensions W x D x H...
12. IO90.195.120.K2.WDC 12.1. INSTALLATION OF THE EXTRACTION UNIT OPTIONAL The extraction unit is for the avoidance of a heat accumulation in the interior during the charging process inside the cabinet. The exhaust air from the cabinet is exhausted directly into the room. Connection to an exhaust duct is not necessary.
12.3. SELF TEST 12.4. ERROR DURING SELF TEST ATTENTION: After pressing the reset button, the self-test begins again. If the error persists, please contact the asecos Service department. 12.5. ERROR AND ALARM OVERVIEW EVENT LED GREEN LED red ACOUSTIC ALARM...
12.6. POTENTIAL FREE ALARM CONTACT NOTE: The potential-free alarm contact is used to connect a signal to a control centre/control room. Direct integration into a fi re alarm control panel (FACP) is not recommended or may only be carried out in consul- tation with the person responsible for the system.
12.8. WARNING MESSAGE >50 °C if connected • Actions Immediate visual inspection of the system by the company’s own qualified personnel. Initiation of necessary actions. If the interior temperature falls below 50 °C, the system returns to normal operation and the visual and acous- tic signals are switched o .
fi re protection and CE conformity are maintained. For this purpose, the cabinet must be handed over to the main factory of asecos GmbH in Gründau, where the specialist department - depending on the degree of damage - will make an assessment of the economic e ciency and technical possibilities of a repair.
Page 20
+34 935 745911 +34 935 745912 info@asecos.es asecos Ltd. asecos asecos Schweiz AG Safety and Environmental Protection Safety and Environmental Protection Inc. Sicherheit und Umweltschutz Profile House 19109 West Catawba Avenue, Suite 200 Gewerbe Brunnmatt 5 Stores Road...
Need help?
Do you have a question about the ION-STORE-90 and is the answer not in the manual?