asecos ION BATTERY STORE User Manual

Safety storage cabinets for the storage of lithium-ion batteries

Advertisement

Quick Links

EP.V.33568.00 / 05.2020
BATTERY STORE
BATTERY STORE PRO
USER MANUAL
Safety storage cabinets for the
storage of Lithium-ion batteries
10 JAHRE GARANTIE*
* Bei jährlicher Beauftragung
des Premium-Tarifs verlängert
sich die Garantie für Ihren ION-
LINE Sicherheitsschrank auf bis
zu 10 Jahre.
Weitere Informationen zu unseren Garantieleistungen finden Sie unter
www.asecos.com/service-leistungen
For detailed information about our warranties please visit
www.asecos.com/service-conditions
10 YEARS WARRANTY*
* Upon conclusion of an asecos
service and maintenance
agreement (PREMIUM
tariff), you will get a warranty
extension for up to 10 years for
your ION-LINE safety storage
cabinet.
EN
EP.V. 10367
10/2013

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ION BATTERY STORE and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for asecos ION BATTERY STORE

  • Page 1 Safety storage cabinets for the storage of Lithium-ion batteries 10 JAHRE GARANTIE* 10 YEARS WARRANTY* * Bei jährlicher Beauftragung * Upon conclusion of an asecos des Premium-Tarifs verlängert service and maintenance sich die Garantie für Ihren ION- agreement (PREMIUM LINE Sicherheitsschrank auf bis tariff), you will get a warranty zu 10 Jahre.
  • Page 2 YOUR PERSONAL DOCUMENTATION TO THE asecos SAFET Y CABINET Dear Customer, you have made a decisive investment in safety for your company by purchasing this asecos safety storage cabinet. You now own an innovative product made of top-quality materials guaranteeing the highest quality standards.
  • Page 3: General Safety Notes

    – refer here to the respective regulations for the prevention of accidents, the VDE regulations and the regulations of the local electricity supply company. • General damage to electronic components is to be repaired without delay by an asecos employee. • Use only intact and undamaged mains cables for the battery charger •...
  • Page 4 2. TRANSPORT 2.3. IN-PLANT TRANSPORT • is also possible without transport locks (inserted as standard in the door joints) ATTENTION: The doors must be locked prior to transport! The extraction unit must be removied from the top of the cabinet ATTENTION: Transport the cabinet in an upright position on a pallet truck, tied and secured against slipping, until the final place of installation is reached.
  • Page 5: Installation

    5. INTERIOR FITTINGS 3. INSTALLATION 5.1. BOTTOM COLLECTING SUMP 3.1. ALIGNMENT OF THE CABINETS According to EN 14470-1: A bottom collecting sump must be installed below the lowest storage level. The bottom collecting sump must be able to hold a minimum volume of 10 % of all the containers stored in the cabinet or at least 110 % of the volume of the largest single container...
  • Page 6 CE conformity are retained. For this purpose the cabinet must be handed over to asecos GmbH‘s main factory in Gründau, where the specialist department – depending on the extent of the damage – will appraise the economic viability and technical 6.
  • Page 7: Safety Checks

    This annual check can be carried out with the necessary care, and for securing your warranty claims in the case of fire, only by an authorised asecos employee (refer also to our service brochure regarding this).
  • Page 8: Connection To The Power Supply

    Connections on the headpiece: Mains plug connector Potential-free switch ATTENTION: contact After pressing the reset button, the self-test begins again. If the error persists, please contact the asecos Service Dept. 10.4. ERROR AND ALARM OVERVIEW Connection to the EVENT LED GREEN...
  • Page 9: Potential-Free Alarm Contact

    10.7. WARNING MESSAGE 10.5. POTENTIAL-FREE ALARM CONTACT NOTE: The potential-free alarm contact is for connecting a signal to a control room/control centre. A direct connection to a fire alarm system is not recommended or may only be done in consultation with those responsible for the system.
  • Page 10: Technical Data

    Exhaust air DN 75 Afterwards the complete system can only be assessed and if possible reset to normal operation by authorised asecos service technicians. At least the fire suppression unit and the smoke detector need to be replaced for this.