8.1.1.1 Parameterisation by the WebConfig interface of the controller
Factory settings of the controller:
IP address: 192.168.4.2, subnet mask: 255.255.0.0
Password: vtem
The password can be changed via the WebConfig interface.
The device on which the WebConfig interface is to be opened must be connected
directly to the Motion Terminal controller. The WebConfig interface for the con-
troller cannot be opened via the Ethernet connection of a bus node in the CPX
terminal.
1. To access the WebConfig interface, establish a connection to the Ethernet
interface of the Motion Terminal controller.
2. Change the IP address and subnet mask of the device used to access the
WebConfig interface to the IP address and subnet mask of the controller.
3. Start the browser and enter the IP address of the controller into the address
line.
4. Use the WebConfig interface ("Configuration" button) for parameterisation of
the Motion Apps for the individual valves.
5. After parameterisation, disconnect the Ethernet interface of the controller to
ensure electromagnetic compatibility.
6. Re-assemble the transparent cover cap of the Ethernet interface to ensure the
degree of protection.
To save the parameterisation permanently on the controller, even with the power
supply switched off, run the corresponding function of the WebConfig interface.
Operation of the WebConfig interface is described in the "Motion Terminal VTEM,
WebConfig interface" QuickGuide è 1.1 Applicable documents.
8.1.1.2 Parameterisation via the controller
Parameterisation via the controller is described in the product manual and in the
CPX terminal manual è 1.1 Applicable documents.
8.2
During commissioning
CAUTION
Injury due to unexpected movement during testing of the product function with
actuator technology and persons in the field of action.
• Keep the range of action of the actuator technology clear.
CAUTION
Injury due to sudden movement of the actuator technology due to pressure
build-up that is delayed or too slow.
• If a safety switch valve is used, the Motion Terminal is operated with external
pilot air, which is branched off before the safety switch valve.
9
Maintenance
9.1
Regular maintenance and repair work to be carried out
Area
Interval
Action
Housing and
every six
Check the relevant tightening torque of the following parts:
– Tie rods
mechanical
months
– Retaining screws of the modules
system
– Mounting screws
Electrical
every six
Check the following:
– Tightening torques for screws of the earthing conductor
months
– Correct seating of all plugs
– Tightening torque of the cable connectors
Tab. 10: Maintenance and repair work
9.2
Clean/replace silencers
NOTICE
Malfunction due to pressure rise in the exhaust ducts due to contamination of
the silencers.
• Clean yellow/black discoloured silencers with petrol or benzene, or replace
them.
9.3
Replace valve or input module
NOTICE
Damage to the product due to replacement of components with compressed air,
operating voltage and load voltage supply switched on (U
• Prior to replacing components, switch off the compressed air, operating voltage
and load voltage supply (U
EL/SEN
1. Unscrew retaining screws of the module.
2. Pull module upward and off the supply plate.
3. Place new module straight from above into the supply plate.
, U
EL/SEN
VAL
, U
).
VAL
4. Screw the module on at first only lightly, and then tighten with the correct
tightening torque è 11.1 Tightening Torques.
10
Diagnostics
Diagnostics are described in this chapter using the LED displays of the Motion
Terminal. Additional diagnostics options è VTEM manual è 1.1 Applicable docu-
ments.
10.1
LEDs on the controller
LED PL (green)
lights
off
Tab. 11: LED PL display (power load, load voltage supply)
LED M (yellow)
lights
flashes
off
Tab. 12: LED display M (Modify)
LED PS (green)
lights
flashes
off
Tab. 13: LED display PS (power system, operating voltage supply)
LED SF (red)
off
lights
Tab. 14: LED display SF (system failure)
LED TP (green)
lights
flashes
).
off
Tab. 15: LED display TP (Ethernet link/traffic)
Meaning
Measure
Voltage is present. No error.
No voltage present.
Check connection of the power
supply.
Meaning
Measure
Configuration active: the Web-
Config interface has write
access, or the PLC is executing
write access on the parameteri-
sation of the controller.
Option for using demo licences
Note the time remaining for the
active.
demo period
Configuration inactive: no
access via the WebConfig inter-
face.
Meaning
Measure
Voltage is present. No error.
Voltage is present but outside
Rectify short circuit/overload.
the tolerance range.
No voltage present.
Check connection of the power
supply.
Meaning
Measure
No error
Voltage of the load voltage
Rectify short circuit/overload.
supply U
is outside the toler-
VAL
ance range.
Access to WebConfig interface
Error on the WebConfig user
is not possible or only condition-
interface or read and remedy via
ally.
PLC, CPX-FMT or FFT.
Meaning
Measure
Network connection is OK (link)
Data traffic (traffic) flashing fre-
quency is dependent on the
traffic.
No network connection/network
If access to the WebConfig inter-
cable is not connected.
face is required:
Check network connection
)
EL/SEN