6.3.2 Changing installation condition

Installation environment
Table 6-3 lists the working environment which equipment installation should comply with.

Table 6-3 Working environment

Physical
address
Construction
Insurance
Working
temperature
Working
humidity
Working air
pressure
ESD
protection
Anti-seismic
grade
Power conditions
Table 6-4 lists power conditions that the RC1201-2GE16E1T1 should comply with.

Table 6-4 Power conditions

AC power
DC Power
Alternative
power
Item
Far from pollution source and environment with dust, harmful gas and
explosives; far away from transformer substation, industrial boiler, heating
boiler wireless interference sources and high-intensity magnetic field
environment.
The equipment room height is not less than 3 m; lay the ESD wrist raised
floor with the load bearing over 600 kg/m
grounding conditions and ensures correct ground connection after
installation.
The power in machine room must be equipped with fuse.
-10° C to 60° C
5%–95% RH (non-condensation)
86–106 kPa
Take effective ESD wrist measures and the electrostatic voltage absolute
value must be smaller than 1000 V.
Up to eight-level seismic grade
Item
The AC rated voltage is 220 V with voltage fluctuation range 176–264 V.
The DC rated voltage is -48 V with voltage fluctuation range -36 V to -72
V. The DC rated voltage is +24 V with voltage fluctuation range +18 V to
+36 V.
A special standby power is preferred to keep equipment working.