Carrier EconoMiSer X Installation, Setup And Troubleshooting Manual page 6

Factory installed option low leak economizer
Hide thumbs Also See for EconoMiSer X:
Table of Contents

Advertisement

Menu
Parameter
SYSTEM
FACTORY DEFAULT
SETUP
(cont)
ADVANCED
MA LO SET
SETUP
FREEZE POS
CO2 ZERO
CO2 SPAN
STG3 DLY
SD DMPR POS
DCVCAL ENA
MAT T CAL
OA T CAL
OA H CAL
RA T CAL
RA H CAL
DA T CAL
CHECKOUT
DAMPER VMIN ---HS
DAMPER VMAX ---HS
DAMPER OPEN
DAMPER CLOSE
CONNECT Y1 ---O
CONNECT Y2 ---O
CONNECT AUX
ALARMS(_)
MA T SENS ERR
CO2 SENS ERR
OA T SENS ERR
DA ENTHL ERR
SYS ALARM
NOTE: The alarms listed are examples. Additional alarms display depending on the parameter settings and configuration.
For example if you do not have a DCV (CO
a
Table 2 illustrates the complete hierarchy. your menu parameters may be different depending on your configuration.
For example if you do not have a DCV (CO
b
When values are displayed, pressing and holding the Y or B button causes the display to automatically increment.
c
n/a = not applicable
d
ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing --- the ERV terminal will be energized.
In the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
Table 2 - - Menu Structure
Parameter
Parameter
Default
Range and Increment
Value
NO
NO or YES
45_F
35 to 55_F;
Incremented by 1_
CLO
CLO or MIN
0ppm
0 to 500 ppm:
Increment by 10
2000ppm
1000 to 3000 ppm;
Increment by 50
2.0h
0 min, 5 min, 15 min, then
15 min intervals. Up to 4 h
or OFF
CLO
CLO or OPN
MAN
MAN (manual)
AUTO
0.0_F
+/ ---2.5_F
0.0_F
+/ ---2.5_F
0% RH
+/ ---10% RH
0.0_F
+/ ---2.5_F
0% RH
+/ ---10% RH
0.0_F
+/ ---2.5_F
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
) sensor, then none of the DCV parameters appear.
2
) sensor, then none of the DCV parameters appear.
2
a
(cont)
b
Resets all set points to factory defaults when set to YES. LCD will briefly
flash YES and change to NO but all parameters will change to the
factory default values.
Temperature to achieve Freeze Protection (close damper and alarm if
temperature falls below setup value)
Damper position when freeze protection is active (closed or MIN POS).
CO
ppm level to match CO
Sensor start level.
2
2
CO
ppm span to match CO
sensor.
2
2
Delay after stage 2 for cool has been active. Turns on 2
st
cooling when economizer is 1
stage. Allows three stages of cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling.
Indicates shutdown signal from space thermostat or unitary controller.
When controller receives 24 Vac input on the SD terminal in conventional
mode, the OA damper will open if programmed for OPN and OA damper
will close if programmed for CLO. All other controls, e.g., fans, etc. will
shut off.
Turns on the DCV automatic control of the dampers. Resets ventilation
based on the RA, OA and MA sensor conditions. Requires all 3 RA, OA
and MA sensors.
Allows for the operator to adjust for an out of calibration temperature
sensor
Allows for the operator to adjust for an out of calibration temperature
sensor
Allows for the operator to adjust for an out of calibration humidity sensor
Allows for the operator to adjust for an out of calibration temperature
sensor
Allows for the operator to adjust for an out of calibration humidity sensor
Allows for the operator to adjust for an out of calibration temperature
sensor
Positions damper to VMIN position
Positions damper to VMAX position
Positions damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test. Make sure
you pause in this mode to allow exhaust contacts to energize due to the
delay in the system.
Positions damper to the fully closed position
Closes the Y1---O relay (Y1---O)
Closes the Y2---O relay (Y2---O)
Energizes the AUX output. If Aux setting is:
S NONE --- not action taken
S ERV --- 24 Vac out. Turns on or signals an ERV that the
conditions are not good for economizing but are good for
d
ERV operation.
S SYS --- 24 Vac out. Issues a system alarm
Alarms display only when they are active. The menu title "ALARMS(_)"
includes the number of active alarms in parenthesis ( ).
When AUX is set to SYS and there is any alarm (e.g., failed sensors,
etc.), the AUX terminal has 24 Vac out.
6
Notes
nd
stage of
nd
stage and mechanical cooling is 2