Carrier EconoMiSer X Installation, Setup And Troubleshooting Manual page 4

Factory installed option low leak economizer
Hide thumbs Also See for EconoMiSer X:
Table of Contents

Advertisement

IMPORTANT: Table 2 illustrates the complete hierarchy. your menu parameters may be different depending on your
configuration. For example if you do not have a DCV (CO
Menu
Parameter
STATUS
ECON AVAIL
ECONOMIZING
OCCUPIED
HEAT PUMP
COOL Y1 ---IN
COOL Y1 ---OUT
COOL Y2 ---IN
COOL Y2 ---OUT
MA TEMP
DA TEMP
OA TEMP
OA HUM
RA TEMP
RA HUM
IN CO2
DCV STATUS
DAMPER OUT
EXH1 OUT
EXH2 OUT
ERV
MECH COOL ON
) sensor, then none of the DCV parameters appear.
2
Table 2 – Menu Structure
Parameter
Parameter
Default
Range and Increment
Value
NO
YES/NO
NO
YES/NO
NO
YES/NO
c
n/a
COOL
HEAT
OFF
ON/OFF
OFF
ON/OFF
OFF
ON/OFF
OFF
ON/OFF
_ _ . __F
0 to 140_F
_ _ . __F
0 to 140_F
_ _ . __F
---40 to 140_F
_ _%
0 to 100%
_ _ . __F
0 to 140_F
_ _%
0 to 100%
_ _ _ppm
0 to 2000 ppm
n/a
ON/OFF
2.0V
2.0 to 10.0V
OFF
ON/OFF
OFF
ON/OFF
OFF
ON/OFF
0
0, 1, or 2
a
b
YES = economizing available; the system can use
outside air for free cooling when required
YES = outside air being used for 1
YES = OCC signal received from space thermostat
or unitary controller.
YES = 24 Vac on terminal OCC.
NO
= 0 Vac on terminal OCC.
Displays COOL or HEAT when system is set to heat pump
(non---conventional)
Y1---I signal from space thermostat or unitary controller for cooling stage
1.
ON
= 24 Vac on terminal Y1---I
OFF = 0Vac on terminal Y1---I
Cool stage 1 Relay Output to stage 1 mechanical cooling (Y1---OUT
terminal)
Y2---I signal from space thermostat our unitary controller for second
stage cooling.
ON
= 24 Vac on terminal Y2---I
OFF = 0 Vac on terminal Y2---I
Cool Stage 2 Relay Output to mechanical cooling (Y2---OUT terminal).
Displays value of measured mixed air from MAT sensor.
Displays --- ---.--- if not connected, short or out---of---range.
Displays when Discharge Air sensor is connected and displays measured
discharge temperature.
Displays _ _ . __F if sensor sends invalid value, if not connected, short or
out---of---range.
Displays measured value of outdoor air temperature.
Displays _ _ . __F if sensor sends invalid value, if not connected, short or
out---of---range.
Displays measured value of outdoor humidity from OA sensor.
Displays _ _% if not connected short, or out---of---range.
Displays measured value of return air temperature from RAT sensor.
Displays _ _ . __F if sensor sends invalid value, if not connected, short
or out---of ---range.
Displays measured value of return air humidity from RA sensor.
Displays _ _% if sensor sends invalid value, if not connected, short or
out---of---range.
Displays value of measured CO
connected, short or out---of---range.
Displays ON if above setpoint and OFF if below setpoint, and ONLY if a
CO
sensor is connected.
2
Displays voltage output to the damper actuator.
Output of EXH1 terminal:
ON
= relay closed
OFF = relay open
Output of AUX terminal; displays only if AUX = EXH2
Output of AUX terminal; displays only if AUX = ERV
Displays stage of mechanical cooling that is active.
4
Notes
st
stage cooling.
from CO
sensor. Invalid if not
2
2