Carrier EconoMiSer X Installation, Setup And Troubleshooting Manual page 5

Factory installed option low leak economizer
Hide thumbs Also See for EconoMiSer X:
Table of Contents

Advertisement

Menu
Parameter
SETPOINTS
MAT SET
LOW T LOCK
DRYBLB SET
ENTH CURVE
DCV SET
MIN POS
VENTMAX With 2---speed
fan units VENTMAX L (low
speed fan) and VENTMAX
H (high speed fan) settings
are required
VENTMAX L
VENTMAX H
VENTMIN With 2---speed
fan units VENTMIN L (low
speed fan) and VENTMIN H
(high speed fan) set
VENTMIN L
VENTMIN H
ERV OAT SP
EXH1 SET With 2---speed
fan units Exh1 L (low speed
fan) and Exh1 H (high
speed fan) settings are
required
Exh1 L
Exh1 H
EXH2 SET With 2---speed
fan units Exh2 L (low speed
fan) and Exh2 H (high
speed fan) settings are
required
Exh2 L
Exh2 H
SYSTEM
INSTALL
SETUP
UNITS DEG
EQUIPMENT
AUX2 I
FAN TYPE
FAN CFM
AUX OUT
OCC
Table 2 - - Menu Structure
Parameter
Parameter
Default
Range and Increment
Value
53_F
38 to 65_F;
increment by 1
32_F
---45 to 80_F;
increment by 1
63_F
48 to 80_F;
increment by 1
ES3
ES1, ES2, ES3, ES4, or
ES5
1100ppm
500 to 2000 ppm;
increment by 100
4.4 V
2 to 10 Vdc
4.4 V
2 to 10 Vdc
or
100 to 9990 cfm
increment by 10
6 V
4.4 V
2.8 V
2 to 10 Vdc
or
100 to 9990 cfm
increment by 10
3.7 V
2.8 V
32_F
0 to 50_F;
increment by 1
50%
0 to 100%;
increment by 1
65%
50%
75%
0 to 100%;
increment by 1
80%
75%
01/01/10
_F or _C
_F
CONV
Conventional or HP
W
SD/W or HP(O)/HP(B)
2 speed
1 speed/2 speed
5000cfm
100 to 15000 cfm;
increment by 100
NONE
NONE
ERV
EXH2
SYS
INPUT
INPUT or ALWAYS
a
(cont)
b
Setpoint determines where the economizer will modulate the OA damper
to maintain the mixed air temperature.
Setpoint determines outdoor temperature when the mechanical cooling
cannot be turned on. Commonly referred to as the Compressor lockout.
Setpoint determines where the economizer will assume outdoor air
temperature is good for free cooling; e.g.: at 63_F unit will economize at
62_F and below and not economize at 64_F and above. There is a
2_F deadband.
Enthalpy boundary "curves" for economizing using single enthalpy.
Displays only if CO
sensor is connected. Setpoint for Demand Control
2
Ventilation of space. Above the setpoint, the OA dampers will modulate
open to bring in additional OA to maintain a space ppm level below the
setpoint.
Displays ONLY if a CO
sensor is NOT connected.
2
Displays only if a CO
sensor is connected. Used for Vbz (ventilation max
2
cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA, OA and MA). In
AUTO mode dampers controlled by CFM.
Displays only if a CO
sensor is connected. Used for Va (ventilation min
2
cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA, OA and MA). Va is
only set if DCV is used. This is the ventilation for less than maximum
occupancy of the space. In AUTO mode dampers controlled by CFM.
Only when AUX1 O = ERV
Setpoint for OA damper position when exhaust fan 1 is powered by the
economizer.
Setpoint for OA damper position when exhaust fan 2 is powered by the
economizer. Only used when AUX is set to EHX2.
Display order = MM/DD/YY
Setting order = DD, MM, then YY .
Sets economizer controller in degrees Fahrenheit or Celsius.
CONV = conventional; HP O/B = Enable Heat Pump mode. Use AUX2 I
for Heat Pump input from thermostat or controller.
In CONV mode: SD + Enables configuration of shutdown (default); W =
Informs controller that system is in heating mode. In HP O/B mode:
HP(O) = energize heat pump on Cool (default); HP(B) = energize heat
pump on Heat.
Sets the economizer controller for operation of 1 speed or 2 speed
supply fan.
This is the capacity of the RTU. The value is found in the Project
Submittal documents for the specific RTU.
S NONE = not configured (output is not used)
S ERV = Energy Recovery Ventilator
S EXH2 = second damper position relay closure for second exhaust fan
S SYS = use output as an alarm signal
When using a setback thermostat with occupancy out (24 Vac), the 24
Vac is input "INPUT" to the OCC terminal. If no occupancy output from
the thermostat then change program to "ALWAYS" OR ad a jumper from
terminal R to OCC terminal.
5