Carrier 62X 03-35 Installation Instructions Manual

Carrier 62X 03-35 Installation Instructions Manual

Dedicated vertical or horizontal outdoor air unit with optional energy conservation wheel

Advertisement

IMPORTANT: This installation instruction contains
basic unit installation information including installation
of field control devices. For information on unit start-up,
service, and operation, refer to the unit Controls, Start-
Up, Operation, Service, and Troubleshooting Instructions
also enclosed in the unit literature packet.
CONTENTS
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Step 1 - Provide Unit Support . . . . . . . . . . . . . . . . . . . 1
• ROOF CURB
Step 2 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2
• POSITIONING
Step 3 - Field Fabricate Ductwork. . . . . . . . . . . . . . 24
for Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . 24
(Gas Heat Units Only). . . . . . . . . . . . . . . . . . . . . . . . . 24
(Hot Water Units Only) . . . . . . . . . . . . . . . . . . . . . . . . 25
Wheel Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Step 10 - Install All Accessories . . . . . . . . . . . . . . . 27
Step 11 - Configure Controls . . . . . . . . . . . . . . . . . . 27
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
PRE-START-UP CHECKLIST . . . . . . . . . . . . . . . . . . CL-1
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . CL-2

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply. Refer to Figure 1
to locate label placement.
Follow all safety codes, including ANSI (American Nation-
al Standards Institute) Z223.1. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53620021-01
Installation Instructions
Page
Printed in U.S.A.
Dedicated Vertical or Horizontal
with Optional Energy Conservation Wheel
Before performing recommended maintenance, be sure
main power switch to unit is turned off and lockout tag is
installed. Electrical shock could cause personal injury.
Puron
®
refrigerant (R-410A) systems operate at higher
pressures than standard R-22 systems. Do not use R-22 ser-
vice equipment or components on Puron refrigerant equip-
ment. If service equipment is not rated for Puron
refrigerant, equipment damage or personal injury may
result.
1. Improper installation, adjustment, alteration, service,
or maintenance can cause property damage, personal
injury, or loss of life. Refer to the User's Information
Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any
phone in your building.
3. IMMEDIATELY call your gas supplier from a neigh-
bor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.

Step 1 - Provide Unit Support

ROOF CURB - Assemble or install accessory roof curb in
accordance with instructions shipped with this accessory. See
submittal drawings for roof curb dimensions. Install insulation,
cant strips, roofing, and counter flashing, if required. For verti-
cal supply and return connections, ductwork can be installed to
roof curb before unit is set in place. Ductwork must be attached
to curb and not to the unit. Curb must be level. This is necessary
to permit unit drain to function properly. Unit leveling tolerance
is ±
1
/
in. per linear ft in any direction. Refer to Accessory
16
Roof Curb Installation Instructions for additional information as
required. When accessory roof curb is used, unit may be in-
stalled on class A, B, or C roof covering material. Carrier roof
curb accessories are for flat roofs or slab mounting.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket with the roof
curb. Improperly applied gasket can also result in air leaks
and poor unit performance. Do not slide unit to position on
roof curb.
Form 62X-1SI
Pg 1
62X 03-35
Outdoor Air Unit
WARNING
CAUTION
WARNING

INSTALLATION

1018
7-18
Replaces: New

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 62X 03-35

  • Page 1: Table Of Contents

    When accessory roof curb is used, unit may be in- sonnel. When working on air-conditioning equipment, observe stalled on class A, B, or C roof covering material. Carrier roof precautions in the literature, tags and labels attached to the unit, curb accessories are for flat roofs or slab mounting.
  • Page 2: Step 2 - Rig And Place Unit

    Clearances Inspect unit Step 2 — Rig and Place Unit — transportation damage. See Tables 1-4 for physical data. See The clearances below are the required distances that the unit Fig. 2 for illustrations on lifting small and large units. File any must be away from objects and other units to allow service ac- claim with transportation agency.
  • Page 3: Installation Onto Curb

    is governed by the type of soil and climatic conditions. The Refer to product submittal drawings to assure proper duct slab must not be in contact with any part of the building opening alignment. wall or foundation. The space between the slab and building CAUTION wall prevents the possibility of transmitting vibration to the building.
  • Page 4 NOTES: 1. Dimensions are in inches. 2. For detailed information on unit dimensions, please refer to a latest edition of Carrier’s Dedicated Outdoor Air Systems Builder. 3. For an exact unit drawing, please refer to the DOAS Builder generated submittal.
  • Page 5 NOTES: 1. Dimensions are in inches. 2. For detailed information on unit dimensions, please refer to a latest edition of Carrier’s Dedicated Outdoor Air Systems Builder. 3. For an exact unit drawing, please refer to the DOAS Builder generated submittal.
  • Page 6 NOTES: 1. Dimensions are in inches. 2. For detailed information on unit dimensions, please refer to a latest edition of Carrier’s Dedicated Outdoor Air Systems Builder. 3. For an exact unit drawing, please refer to the DOAS Builder generated submittal.
  • Page 7 NOTES: 1. Dimensions are in inches. 2. For detailed information on unit dimensions, please refer to a latest edition of Carrier’s Dedicated Outdoor Air Systems Builder. 3. For an exact unit drawing, please refer to the DOAS Builder generated submittal.
  • Page 8 NOTES: 1. Dimensions are in inches. 2. For detailed information on unit dimensions, please refer to a latest edition of Carrier’s Dedicated Outdoor Air Systems Builder. 3. For an exact unit drawing, please refer to the DOAS Builder generated submittal.
  • Page 9 2. For detailed information on unit dimensions, please refer to a latest edition EXHAUST 17 1/8 of Carrier’s Dedicated Outdoor Air Systems Builder. 3. For an exact unit drawing, please refer to the DOAS Builder generated submittal. Fig. 5 — Unit Dimensions — 62X BXL Cabinet, High Capacity (Size 20), ERV,...
  • Page 10 NOTES: 1. Dimensions are in inches. 2. For detailed information on unit dimensions, please refer to a latest edition of Carrier’s Dedicated Outdoor Air Systems Builder. 3. For an exact unit drawing, please refer to the DOAS Builder generated submittal.
  • Page 11 NOTES: 1. Dimensions are in inches. 2. For detailed information on unit dimensions, please refer to a latest edition of Carrier’s Dedicated Outdoor Air Systems Builder. 3. For an exact unit drawing, please refer to the DOAS Builder generated submittal.
  • Page 12 NOTES: 1. Dimensions are in inches. 2. For detailed information on unit dimensions, please refer to a latest edition of Carrier’s Dedicated Outdoor Air Systems Builder. 3. For an exact unit drawing, please refer to the DOAS Builder generated submittal.
  • Page 13 NOTES: 1. Dimensions are in inches. 2. For detailed information on unit dimensions, please refer to a latest edition of Carrier’s Dedicated Outdoor Air Systems Builder. 3. For an exact unit drawing, please refer to the DOAS Builder generated submittal.
  • Page 14 NOTES: 1. Dimensions are in inches. 2. For detailed information on unit dimensions, please refer to a latest edition of Carrier’s Dedicated Outdoor Air Systems Builder. 3. For an exact unit drawing, please refer to the DOAS Builder generated submittal.
  • Page 15 NOTES: 1. Dimensions are in inches. 2. For detailed information on unit dimensions, please refer to a latest edition of Carrier’s Dedicated Outdoor Air Systems Builder. 3. For an exact unit drawing, please refer to the DOAS Builder generated submittal.
  • Page 16 Table 1 — Physical Data — 62X A Cabinet UNIT 62X A CABINET NOMINAL CAPACITY (TONS) COMPRESSOR Unit without ERV Quantity/Unit…Model 1...ZPD34 1...ZPD42 1...ZPD51 1...ZPD54 1ZPD...72 1ZPD...83 Unit with ERV Quantity/Unit…Model 1...ZPD34 1...ZPD42 1...ZPD51 1...ZPD61 1ZPD...72 1ZPD...83 Number of Refrigerant Circuits Pre-Charged REFRIGERANT TYPE R-410A...
  • Page 17 * Optional. — Electronically Commutated Motor NOTE: For unit and component weights, refer to the latest edition of — Energy Recovery Ventilator Carrier's Dedicated Outdoor Air Systems Builder. — Fins per Inch — Liquid Propane — Outdoor Air — Silicon-Controlled Rectifier...
  • Page 18 Table 2 — Physical Data — 62X, B-BXL Cabinet UNIT 62X B CABINET NOMINAL CAPACITY (TONS) 17.5 COMPRESSOR Unit without ERV 1...ZPD51, 1...ZPD61, 1...ZPD91, 1...ZPD103, 1...ZPD72, 1...ZP51 1...ZP61 1...ZP91 1...ZPD103 Quantity/Unit … Model 1...ZPD34 1...ZPD42 1...ZPD51 1...ZPD54 1...ZPD72 1...ZPD83 1...ZP72 or 2...ZPD72 2...ZPD51 2...ZPD61...
  • Page 19 Table 2 — Physical Data — 62X, B-BXL Cabinet (cont) UNIT 62X B CABINET NOMINAL CAPACITY (TONS) 17.5 OUTDOOR AIR FILTERS Quantity … Size (in.) with ERV Standard 2-in. MERV 8 2...24x24 4...16 x 25 2...16x25, 2...20x25 Use C Cabinet Optional 4-in.
  • Page 20 Table 3 — Physical Data — 62X, C-CXL Cabinet UNIT 62X C CABINET NOMINAL CAPACITY (TONS) 17.5 COMPRESSOR Unit without ERV 1...ZPD61, 1...ZPD72, 1...ZPD91, 1...ZPD120, 1...ZPD137, 1...ZPD182, 1...ZPD51, 1...ZPD103, 1...ZP61 1...ZP72 1...ZP91 1...ZP120 1...ZP137 1...ZP182 Quantity/Unit … Model 1...ZPD72 1...ZPD83 1...ZP51 or 1...ZP103 or 2...ZPD51...
  • Page 21 * XL gas heater only available in 10:1 modulation. — Electronically Commutated Motor — Energy Recovery Ventilator NOTE: For unit and component weights, refer to the latest edition of Carrier's Dedi- — Fins per Inch cated Outdoor Air Systems Builder. —...
  • Page 22 Table 4 — Physical Data — 62X, D-DXL Cabinet UNIT 62X, D CABINET NOMINAL CAPACITY (TONS) COMPRESSOR Unit without ERV 1...ZPD103, 1...ZPD120, 1...ZPD137, 1...ZPD182, Quantity/Unit ... Model 1...ZP103 or 1...ZP120 or 1...ZP137 or 1...ZP182 or 2...ZPD103 2...ZPD120 2...ZPD137 2...ZPD182 Unit with ERV 1...ZPD103, 1...ZPD137, 1...ZPD154,...
  • Page 23 Electronically Commutated Motor kW SCR electric heater not available. — Energy Recovery Ventilator — Fins per Inch NOTE: For unit and component weights, refer to the latest edition of Carrier's — Liquid Propane Dedicated Outdoor Air Systems Builder. — Outdoor Air —...
  • Page 24: Step 3 - Field Fabricate Ductwork

    NOTE: For weight references, consult the DOAS Builder pro- Step 5 — Install External Trap for Condensate gram submittal. The unit’s -in. condensate drain connection is lo- Drain — cated on the side of the unit. Refer to the DOAS Builder gener- On vertical Step 3 —...
  • Page 25: Step 7 - Install Hot Water Or Steam Piping (Hot Water Units Only)

    exchanger. The heater should not be placed back in oper- IMPORTANT: Natural gas pressure at unit gas connection ation until the cause of the rollout condition is identified. must not be less than 5.0 in. wg or greater than 13.0 in. wg The rollout switch can be reset by pressing the button on for all heat sizes.
  • Page 26 wiring connections on units with factory disconnects should be This amount of phase imbalance is satisfactory as it is be- made at the line side of the disconnect switch. low the maximum allowable 2%. The internal power and control wiring of these units is fac- IMPORTANT: If the supply voltage phase imbalance is tory installed and each unit is thoroughly tested prior to ship- more than 2%, contact your local electric utility company...
  • Page 27: Step 9 - Open Exhaust Damper

    in the cabinet. The sensor is connected to the unit controller as indicated in the wiring diagram with 18 AWG (American Wire Gage) shielded wire. Do not run the sensor wiring in the same conduit as high voltage wiring. A zone temperature sensor (ZS) may be provided as an ac- cessory with units that have ordered the space temperature override control function.
  • Page 28 • SF-VSC: Supply Fan with Variable Speed Control — or more, the compressor turns back on. If there is a cur- The SF-VSC will modulate its speed based upon the SF rent call for first stage cooling and compressor no. 1 is Differential Pressure Transmitter (SF-DPT) signal to shut down due to an alarm (HPS1, LPS1, or DX LAT1), maintain the supply duct static pressure set point.
  • Page 29 Heating Mode — Heating mode is available when the OAT is Safety Switches below the OAT heating upper limit (60°F, adjustable) and there • High Pressure Switch (HPS1): If HPS1 is open, com- is a demand to temper outdoor air to room neutral conditions. pressor no.
  • Page 30: Step 12 - Test Mode And Fan Balancing

    Table 10 — Ambient Charge — 100% Outside Air Step 12 — Test Mode and Fan Balancing — and Combined Unit Subcool and Superheat For fan balancing, the manual override function should be used. This function manually enables one to set the operational AMBIENT 95°F 85°F...
  • Page 31 MSP-CC1 R-## R-## R-## BL-## BL-## BL-## BK-## BK-## BK-## CCH1 G-14 R-14 CC1-A1 BK-14 OUTDOOR FAN MOTOR VFD (OF1VFD)CONTROL TERMINAL STRIP OF1VFD CC1-A1 +12-30VDC White 0-10vdc DI-C Black Common MSP-OF1 OF1VFD R-14 R-14 R-14 BL-14 BL-14 BL-14 OFM1 G-14 BK-14 BK-14 BK-14...
  • Page 32 NOTE: SEE “T1” ON SHEET 1 Line 96 VA NOTE: SEE “T3” ON SHEET 1 FOR WIRING CONTINUATION Voltage CLASS 2 FOR WIRING CONTINUATION 50/60HZ PM AUX 50/60HZ R-14 R-14 G-14 G-14 R-14 BL-14 R-14 Remove jumper when field installed safe es are used UNLOADER SOLENOID #1 Enable Unloader #1...
  • Page 33 CONTINUED ON SHEET 2 BOS1 Enable Supply Fan SF1R EF1R 136, 207, Enable Hot Gas Reheat Enable Wheel Motor Heat Enable See separate Modula ng Gas Furnace Drawing BCTL Enable Hea ng OADA Enable Outdoor Air Damper Actuator 24VAC Fig. 14 — Installation Wiring Diagram (cont)
  • Page 34 MODULATING REHEAT CONTROL VALVE BOARD When using an SDR-3/3X Valve (0564P-0002), use SDR 3/3X SW1 settings. All other modulating valves, 40 VA use SW1 Normal Settings. See label on valve to CLASS 2 insure the proper setting is used for SW1. 60 HZ For normal opera on the “CN1"...
  • Page 35 FIELD INSTALL EQUIPMENT TOUCH SEE TB4 ON UNIT LonWorks Card (op onal) WIRING DIAGRAM Green White Black ZS Room Port 2b Sensor Power To wall mount the 24VAC External 3V Li um Ba ery Equipment Touch, remove Ba ery Off CR-123A + 3V the factory installed cable...
  • Page 36 SEE TB4 ON UNIT WIRING DIAGRAM 24VAC Gnd 16 Universal UI-16 Inputs 9-16 + 15 0-5V Therm/ Gnd 14 FIELD WIRED; PROVIDED BY Power UI-15 OTHERS + 13 (EMR is disabled by Defualt) Gnd 12 Install Condensate Overflow Switch “COS” At Lowest UI-14 Point of Drain Pan + 11...
  • Page 37 LEGEND - ITEMS INSIDE CONTROL PANEL LEGEND - ITEMS OUTSIDE CONTROL PANEL FUNCTIONAL FUNCTIONAL ITEM LINE NUMBER DESCRIPTION ITEM LINE NUMBER DESCRIPTION DESIGNATION DESIGNATION Supply Fan Motor Relay BCTL BCTL MSP-SF Motor Starter Protec on-Supply Fan BOS1 Bleed-Off Solenoid no. 1 SF-VFD Supply Fan-Variable Frequency Drive CCH1...
  • Page 38 GAS FURNACE POWER SUPPLY FOR 460 VOLT UNITS 2 amps fuse : 500VA 2 amps fuse : 500VA 3 amps fuse : 750VA 3 amps fuse : 750VA BL-14 Class CC, BL-14 600volts, BK-14 BK-14 Time Delay Class CC, 460V 500 VA R-14 600volts,...
  • Page 39: Maintenance

    The mixing of different lation and service of equipment sold and supplied by Carrier, as types of thickeners may destroy the composition and well as conform to all requirements set forth in the manuals and physical properties of the grease.
  • Page 40: Troubleshooting

    cessive pressure drop, then wheel cleaning should be per- MANUAL SAFETY SHUT OFF VALVE — Check for gas formed as follows: leaks. 1. Using a standard shop vacuum, vacuum any debris from DIRECT SPARK IGNITER — Check for cracked ceramics, both faces of the wheel.
  • Page 41 Table 13 — Compressor PROBLEM POSSIBLE CAUSE SOLUTION Power off, loose electrical connections or fuse open Check disconnect switch, fuses and wiring. Check voltage to contactor coil, transformer slave Compressor contactor not closing relay, thermostat. If compressor is hot, allow 2 hours to cool – see Internal compressor thermal overload open below.
  • Page 42 Table 14 — Refrigeration Circuit PROBLEM POSSIBLE CAUSE SOLUTION Air noise Check ductwork. Air velocity too high. Check for adequate control voltage. Check for shorts Chattering contactor or breaks. Check thermostat. Check contactor Noisy operation points. Dampen by taping or clamping. Bend tubing away Tubing rattle from contact, where possible.
  • Page 43 Table 15 — Variable Speed Head Pressure Control PROBLEM POSSIBLE CAUSE SOLUTION No 24V control voltage Check for 24 VAC at control. Check alignment of capillary fitting. Schrader valve No input pressure to control depressor must depress Schrader valve enough to allow pressure into capillary.
  • Page 44 Table 16 — Energy Wheel Conservation PROBLEM POSSIBLE CAUSE SOLUTION Incorrect wheel rotation speed Check wheel rotation speed. Check wheel integrity and seals. Adjust and/or replace Worn wheel media or worn/out-of-place seals seals. Inadequate wheel performance Unanticipated entering air conditions Check entering air conditions and compare to design.
  • Page 45 Table 19 — Mapping Points for Multiple Unit Styles and Types BACNET MODBUS LONWORKS READ POINT NAME OBJECT NAME OBJECT WRITE TYPE TYPE NUMBER TYPE ADDRESS SNVT NAME SNVT Alarm Reset alarm_reset Coil nviAlarmReset SNVT_switch(95) Alarm Status alarm_status Discrete Input 10103 nvoAlarmStat SNVT_count_inc(9)
  • Page 46 Table 19 — Mapping Points for Multiple Unit Styles and Types (cont) BACNET MODBUS LONWORKS READ POINT NAME OBJECT NAME OBJECT WRITE TYPE TYPE NUMBER TYPE ADDRESS SNVT NAME SNVT Digital Compressor #1 dig_c1_pct 6401 Input Register 30123 nvoDigC1Pct SNVT_lev_percent(81) Percent Digital Compressor #2 dig_c2_pct...
  • Page 47 Table 19 — Mapping Points for Multiple Unit Styles and Types (cont) BACNET MODBUS LONWORKS READ POINT NAME OBJECT NAME OBJECT WRITE TYPE TYPE NUMBER TYPE ADDRESS SNVT NAME SNVT HPS1 STOP hps1_stop_alarm Discrete Input 10120 HPS2 ALARM hps2_alarm Discrete Input 10133 HPS2 STOP hps2_stop_alarm...
  • Page 48 Holding Register 40021 nvoHtgZatSp SNVT_temp_p(105) © Carrier Corporation 2018 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53620021-01 Printed in U.S.A. Form 62X-1SI Pg 48...
  • Page 49: Pre-Start-Up Checklist

    Serial Number ______________________________________ PRESTART-UP CHECKLIST  The unit is free of damage. If damage exists, contact your local Carrier representative.  The unit power feed is installed. Voltage and phasing have been verified to be correct.  The power feed meets the MCA requirements as indicated on the unit label.
  • Page 50: Start-Up Checklist

    Software Date ______________________________________ CHECKLIST  Verify the unit is free of damage. If damage exists, contact your local Carrier representative.  Check the unit power feed for voltage and phasing.  Check unit power wiring, verify correct fuses/breakers are installed.
  • Page 51 UNIT START-UP: ELECTRICAL UNIT SUPPLY VOLTAGE L1-L2 _____________ L2-L3 ________________ L3-L1 ________________ COMPRESSOR 1 AMPS C1-L2 _____________ C1-L2 ________________ C1-L3 ________________ COMPRESSOR 2 AMPS C2-L1 _____________ C2-L2 ________________ C2-L3 ________________ SUPPLY FAN AMPS CV________________ VAV*_________________ EXHAUST FAN AMPS CV________________ VAV*_________________ ECW MOTOR AMPS ___________________ _____________________...
  • Page 52 Pre-Filter Size _____________________________________________________ Quantity__________________________ ECW Belt Part Number _____________________________________________ Size _____________________________ © Carrier Corporation 2018 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53620021-01 Printed in U.S.A.

Table of Contents