Summary of Contents for Lutron Electronics CGP2730
Page 1
Ne pla cez pas HW -RP ou HW -RP M- 4U -12 0 CGP2730 Subplate M- 4A- 120 dan s ce lieu mo dul es Compatible Enclosure Dimensions Enclosure Preparation CA UT ION | PR EC AU CIÓ...
Page 2
16 A total per module (1 circuit/module), 5 A per output (1/4 HP motor, 1 per output), 4 outputs per module 4FSQ 8 A total per module (1 circuit/module), 2 A per output (single ceiling fan), 4 outputs per module Installation Guide for CGP2730 Dimming and Switching Subplate ®...
Page 3
37 in (939.8 mm) (Sidewall) Existing UL Label Do not remove the existing UL label, this will be needed to confirm UL compliance of the enclosure. Front View Side View Installation Guide for CGP2730 Dimming and Switching Subplate 3 ® ®...
Page 4
Compatible Enclosure Labeling Enclosure Label Installation This page describes how and where to install the labels provided by Lutron. These labels contain torque and wiring information in addition to bypass jumper placement. Enclosure and Subplate Guidelines • For indoor use only with NEMA/UL Type 1 listed enclosure, IP20. •...
Page 5
Torque the screws Drill holes using a #29 bit and vacuum to 17 in-lbs (1.92 N • out any metal shavings. Installation Guide for CGP2730 Dimming and Switching Subplate 5 ® ®...
Page 6
Module and Module Interface (MI) Installation Module installation: Secure up to 8 modules using three screws for each module. Place the tab on the bottom of the module around the single screw and pull up. This will align the top two screws.
Page 7
Vor dem Siche rungs l, schal ten autom aten Sie bitte und siche und Haup alle rn diese tscha lter in der AUS- Posit ion. HWI-MI-120 Power Wiring: Installation Guide for CGP2730 Dimming and Switching Subplate 7 ® ®...
Page 8
Module Specific Installation Wiring • Use the following information to wire the newly installed modules. • Terminal blocks for 4U, 4J, and 4FSQ modules come pre-installed on the subplate. • Terminal blocks for 4M and 4R modules are included with the modules and should be installed in place of the default terminal blocks as needed.
Page 9
Secure wire bundles with zip-ties, neatly out of the way of anything that can damage the wires. Switching Module (4R) 4-Circuit BLACK WIRES RED WIRES WHITE WIRE Terminal Blocks Installation Guide for CGP2730 Dimming and Switching Subplate 9 ® ®...
Page 10
Module Specific Installation Wiring (continued) • Use the following information to wire the newly installed modules. • Terminal blocks for 4U, 4J, and 4FSQ modules come pre-installed on the subplate. • Terminal blocks for 4M and 4R modules are included with the modules and should be installed in place of the default terminal blocks as needed.
Page 11
DO NOT TIE NEUTRAL • Run wiring so that line (mains) voltage wiring will be at least 6 ft (1.83 m) from sound or electronic equipment and its wiring. BUSSES TOGETHER Installation Guide for CGP2730 Dimming and Switching Subplate 11 ® ®...
Page 12
Module Specific Load Wiring Load Circuit Wiring: 4U/4J/4FSQ (single typical dimming/switching leg shown for each module type) • Connect Hot load wiring to the appropriate load terminal set for each circuit and Neutral to the Neutral bus. • The Dimmed Hot (DH) and/or Switched Hot (SH) terminal blocks are grouped by a module (4 output circuits each) in numbered order in the top right of the subplate.
Page 14
PELV (Class 2: USA) Wiring CGP2730 MI Wiring: Terminate the processor communication link on the last module interface. If any of the module interfaces are located more than 50 ft (15.25 m) from the processor, the last module interface on the chain must utilize a terminator across terminals 3 and 4.
Page 15
Bypass jumpers come pre-installed in the module terminal blocks for your convenience and will allow for temporary lighting until your system is programmed. Installation Guide for CGP2730 Dimming and Switching Subplate 15 ® ®...
Page 16
Activate Loads in Bypass A. Complete load wiring. B. Check that the bypass jumpers are in place. These jumpers protect from load faults and must be used to check load wiring when it is installed or modified. WARNING! Shock hazard. May result in serious injury or death if panel is not wired correctly.
Page 17
Module with 4 outputs shown Notice: Reuse the bypass jumpers whenever work is being done on a load. Damage caused by short-circuits and mis-wiring is not covered by the product warranty. Installation Guide for CGP2730 Dimming and Switching Subplate 17 ® ®...
Page 18
Included Front Cover HWR-COVER-001 CGP2730 subplate dimming/switching solutions are designed to only work inside compatible LiteTouch or Savant enclosures with corresponding Lutron provided front cover part #HWR-COVER-001. This front cover is specifically designed to provide proper convection cooling while safely preventing access to line voltage sections of the panel.
Page 19
Notes Installation Guide for CGP2730 Dimming and Switching Subplate 19 ® ®...
Need help?
Do you have a question about the CGP2730 and is the answer not in the manual?