ABB COPA-XT DT43F Instruction Bulletin page 16

Electromagnetic flowmeter in 2-wire technology with pulsed dc magnetic fields
Table of Contents

Advertisement

Electromagnetic Flowmeter COPA-XT
Binary Output (terminals V8, V9)
The output can be configured as a pulse or system alarm
output. The output conforms to the Standard VDI/VDE 2188.
Scaled Pulse Output (terminals V8, V9)
Scaled pulse output max. 100 Hz, pulse factor between
0.001 and 1000 as a multiplier for the value indicated in the
3
display (1 pulse/m
* 1000). The pulse width can be set from
0.100 ms to 2000 ms.
Configuration
Terminal function
Operating voltage
Operating current and frequency 0 mA ≤ U
Contact Output (terminals V8, V9)
The following functions can be assigned in the software:
System Monitor closed or open contact
Forward/Reverse, closed for forward flow direction
Max-Alarm, Min-Alarm, closed or open contact
HART-Protocol
The HART-Protocol provides for communication between a
process control system or handheld terminal and an EMF field
instrument. The digital communication utilizes an AC signal
superimposed on the current output which does not affect any
Fig. 23
Communication with HART-Protocol
Transmission Mode
FSK-Modulation on the 4-20 mA current output per Bell 202
Standard. Max. signal ampl. 1.2 mA
Load (Current Output)
Min.: > 250 Ω, max. see Fig. 20.
Cable
AWG 24 twisted
Max. Cable Length
1500 m
Baudrate
1200 Baud. Logic 1: 1200 Hz; Logic 0: 2200 Hz
10
Optocoupler passive (Standard)
V8, V9
16 V ≤ U
≤ 30 V
CEH
0 V ≤ U
≤ 2 V
CEL
≤ 0.2 mA
CEH
2 mA ≤ U
≤ 220 mA
CEL
≤ 100 Hz
f
max
pp
other instruments connected to the current output circuit.
Current output 4-20 mA. terminals: +/-