ABB COPA-XT DT43F Instruction Bulletin page 25

Electromagnetic flowmeter in 2-wire technology with pulsed dc magnetic fields
Table of Contents

Advertisement

Submenu/Parameter
Submenu
Alarm
ENTER
Submenu
Current Output
ENTER
Submenu
Data Link
ENTER
Submenu
Function Test
ENTER
Electromagnetic Flowmeter COPA-XT
Entry Type
Unit name
kga /s /min /h
Prog. Units
Without Density
from table/numeric
Error Register
0 . . . 3 . . .
Max-Alarm
105 %
Min-Alarm
10 %
Iout at Alarm
105 %
Instr. Address
0
Communication
HART
from table/numeric
Function Test
Iout
Comments
Four character name for the user configurable units.
Programmable units for mass (with density) or
volume (without density) flowrate units
Exit from submenu
C/CE
All detected errors (Error 0-9, A, B, C) are stored.
The error register can be cleared with ENTER.
Alarm limit, range 0 - 105 % of the flow range setting.
Alarm limit, range 0 - 105 % of the flow range setting.
Exit from submenu
C/CE
Current output during an alarm condition, can be set to
0 % or 105 %
Error 3 Flowrate > 105 %, always set to 22 mA %
Exit from submenu
C/CE
Instrument address: 0-99
If multiple instruments are connected to a single bus, then each
instrument must have a unique address.
Activate the HART-Communication:
HART or off
Exit from submenu
C/CE
Function test of current output, enter value in mA
Function test of pulse output 1 Hz
For detailed information see Sect. 6.2
19