Hdsl Alarm Thresholds Screen; System Alarm Types - ADC PG-PLUS PLL-720 Technical Practice

Table of Contents

Advertisement

SCP-PLL720-020-03H
Alarm
Value
COLU-RT Mismatch
NR, NA, MN, MJ, CR
(MISMATCH)
No RT S/W
NR, NA, MN, MJ, CR
(NORTSWA)
EEPROM Failure
NR, NA, MN, MJ, CR
(BKUPMEMP)

HDSL Alarm Thresholds Screen

Provides a means to provision the threshold crossing values for the 24-hour ES count and low margin dB.
Table 10
lists the fields of the HDSL alarm thresholds and the default factory values.
1.
At the CONFIG submenu, select HDSL Alarm Thrshlds, and press
2.
You can perform the following tasks:
a. To set the 15-minutes errored seconds threshold for the COLU, select the Errored Seconds (ES 15 Min)
field in the
COLU ALARM THRESHOLD
b. To set the 24-hour errored seconds threshold for the COLU, select the Errored Seconds (ES 24 Hr) field
in the
COLU ALARM THRESHOLD
c. To set the 15-minutes unavailable seconds threshold for the COLU, select the Unavailable Seconds (UAS
15 Min) field in the
d. To set the 24-hour unavailable seconds threshold for the COLU, select the Unavailable Seconds (UAS 24
Hr) field in the
e. To set the low margin threshold for the COLU, select the Low Margin (MAR) field in the
column, and type in the desired value.
THRESHOLD
PLL-720, PLL-721 List 2's
Table 9.
Description
Incompatible COLU and RT units have been installed. For
example, a Dual 2 POTS COLU has been connected to a 2
ISDN RT.
RT has no application software and is awaiting software
download.
EEPROM failure.
column, and type in the desired value.
column, and type in the desired value.
COLU ALARM THRESHOLD
COLU ALARM THRESHOLD
January 6, 2003

System Alarm Types

ENTER
column, and type in the desired value.
column, and type in the desired value.
Configuration Submenu
Default
MN
MN
MN
to view the screen.
COLU ALARM
39