Siemens SIMATIC NET RUGGEDCOM RSG2300P Installation Manual page 53

Rugged ethernet switches
Hide thumbs Also See for SIMATIC NET RUGGEDCOM RSG2300P:
Table of Contents

Advertisement

Certification
6.2 EMC and Environmental Type Tests
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Radiated RFI
Fast Transient
Oscillatory
HV Impulse
Oscillatory
Magnetic Field
Environmental Type Tests
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60068-2-6
IEC 60255-21-1
IEC 60068-2-27
IEC 60255-21-2
44
Description
ESD
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Dielectric
Signal Ports
Strength
DC Power Ports
AC Power Ports
Damped
Enclosure Ports
Test
Cold Temperature
Humidity (Damp Heat, Cyclic)
Description
Dry Heat
Vibration
Shock
Test Levels
±2 kV
±8 kV
±15 kV
35 V/m
4 kV @ 2.5 kHz
4 kV
4 kV
4 kV
2.5 kV Common Mode @ 1 MHz
2.5 kV Common
1 kV differential mode @ 1 MHz
2.5 kV Common
1 kV differential mode @ 1 MHz
5 kV (Fail-Safe Relay Output)
5 kV
5 kV
2 kV
2 kV
2 kV
100 A/m
Test Levels
Test Ad
-40 °C (-40 °F), 16 Hours
Test Bd
85 °C (185 °F), 16 Hours
Test Db
95% (Non-Condensing),
55 °C (131 °F), 6 Cycles
2g @ 10-150 Hz, 2 hours per axis
30 g @ 11 ms
Installation Manual, 04/2022, C79000-G8976-1047-18
RUGGEDCOM RSG2300P

Advertisement

Table of Contents
loading

Table of Contents