Nailor 37S Manual page 7

Low profile fan powered terminal unit with epic ecm or psc motor
Table of Contents

Advertisement

DESCRIPTION:
• Only 11" (279) high.
• 20 ga. (1.0) galvanized
steel construction.
• 16 ga. (1.6) galvanized
steel inclined blade damper.
45° rotation. CW to close.
• 'Stealth
'
tuned
inlet
TM
attenuators (2). Shipped loose
for field mounting.
• Multi-point
averaging
Diamond Flow sensor.
• Access panels top and
bottom.
• 1/2"
(13)
dual
density
insulation, exposed edges
coated
to
prevent
air
erosion. Meets requirements
of NFPA 90A and UL 181.
• Single
point
electrical
and/or pneumatic main air
connection.
• Discharge
opening
for
flanged duct connection.
• Full
primary
air
valve
low voltage NEMA 1 type
enclosure
for
factory
mounted DDC and analog
electronic controls.
• Controls
mounted
as
standard on RH side as
shown. Terminals ordered
with LH controls (optional)
are inverted.
MOTOR OPTIONS:
q
Energy
efficient
PSC
fan motor with overload
protection. Solid state
fan speed controller with
minimum voltage stop.
q
Ultra-high efficiency ECM
fan
motor.
EPIC
fan
volume controller.
OPTIONS:
q
Filter frame and 1" (25)
disposable filter.
q
Toggle disconnect switch.
q
Steri-liner.
q
Fiber-free liner.
q
Solid metal liner.
q
Perforated metal liner.
q
Fan unit fusing.
q
Hanger brackets.
q
Left-hand controls location.
q
FN2 90° Line Voltage
Enclosure.
q
FN3 Remote Line
Voltage Enclosure
(see submittal FN3).
q
Special features
____________________.
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
LOW PROFILE FAN POWERED TERMINAL UNIT WITH
EPIC ECM OR PSC MOTOR
'STEALTH
CONSTANT OR VARIABLE VOLUME
MODELS: 37SST, 37SEST AND 37SWST • UNIT SIZE 4
Model 37SST and Basic Unit
41 1/2"
(114)
MULTI-POINT
AIRFLOW
SENSOR
PRIMARY
AIR
33 1/2"
(851)
11"
(279)
PRIMARY
AIR
Dimensional Data
Electrical Data
The EPIC ECM is a variable horsepower motor.
*
Refer to Selectworks schedule for actual power consumption.
FLA = Full load amperage. All motors are single phase/60 Hz.
' • SERIES FLOW
TM
49 3/4" (1264)
13 1/4"
(337)
INDUCED
19 1/2"
AIR
(495)
L
W
2
14" (356)
10" (254)
5 3/4" (146)
INDUCED
AIR
5 1/2"
(140)
OPTIONAL
HINGED FAN
PRIMARY AIR
CONTROLS
VALVE CONTROLS
H
ENCLOSURE
ENCLOSURE
2
For heat options; see page 2 and 3.
DATE
8 - 13 - 19
IH
P
DH
FAN
W
FAN
15"
(381)
6 3/4"
(171)
OPTIONAL
90° FN2
HINGED FAN
OPTIONAL
CONTROLS
INDUCED
ENCLOSURE
AIR FILTER
11" (279)
Page 1 of 3.
Dimensions are in inches (mm).
B SERIES
SUPERSEDES DRAWING NO.
3700
7 - 18 - 17
IW
11 1/4"
(286)
83"
DW
(2108)
11 1/4"
(286)
B
37SST-2