CONTROL SEQUENCE B7
COOLING WITH ELECTRIC HEAT AND NIGHT TEMPERATURE
SET-BACK CYCLE
Sequence of Operation:
Day/Occupied Cycle
The terminal fan is interlocked by way of a positive pressure airflow switch, which
automatically energizes the fan upon sensing central system start up.
With room temperature at set point, unit delivers minimum cooling airflow and
maximum induced plenum air. On a rise in room temperature, the thermostat regulates
the controller/actuator to increase primary airflow. As more cold air is supplied to the
fan section, less warm air is induced from the ceiling plenum.
When the room temperature exceeds the setpoint by 2°F (1.1°C) or more, primary
airflow is maintained at the maximum setting. The maximum setting is usually the same
as the total fan volume setting.
On a decrease in room temperature, the thermostat regulates the controller/actuator to
decrease the airflow and as less cold air is supplied to the fan section, more warm air is
induced from the ceiling plenum. If room temperature continues to drop, minimum primary
airflow is maintained and at 0.8°F (0.4°C) below setpoint, the first stage of electric heat is
energized. The optional second heat stage is energized at 1.6°F (0.9°C) below setpoint.
An increase in room temperature de-activates the heat stages at 1.2°F and 0.4°F
(0.7°C and 0.2°C) below setpoint.
Primary airflow is held constant in accordance with thermostat demand. Any changes
in duct air velocity due to static pressure fluctuations are sensed and compensated for,
resulting in pressure independent control.
Night/Unoccupied Cycle.
Airflow switch de-energizes fan upon loss of primary (central) air and activates the night side
of the thermostat through DPDT relay. Primary air damper cycles closed.
Upon a call for heat, the thermostat will override the airflow switch and will cycle the unit fan
followed by the supplementary heat intermittently to maintain night set-back setpoint temperature.
:
Note
Room thermostat has individually adjustable night and day setpoints. They can
be adjusted to be within 1°F (0.55°C) of each other.
Minimum and maximum primary airflow limits are adjusted underneath the thermostat cover.
Options:
Thermostat Scale Plate:
(Thermostat includes backing plate for 2" x 4" electrical box).
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
ANALOG ELECTRONIC CONTROL
FAN POWERED TERMINAL UNIT • SERIES FLOW
CONSTANT VOLUME • PRESSURE INDEPENDENT
MODELS: 35SE, 35SEST, 37SE AND 37SEST B7
CSP-5002
V
N
M
M
N
O
A
I
O
O
R
X
N
M
U
24V
M
A
METER
T
AC
X
%
RED-CLS
M
GRN-OPN
I
N
C
LED
L
CCW CW
O
S
E
AIRFLOW SWITCH
C
NO
NC
°F or
°C
CTE-5105 ROOM THERMOSTAT (DA/DA) NIGHT/DAY DUAL SET POINT
DPDT
12
RELAY
V1 T3 R1 T1 +
V
V1
T3
T1
+
ELECTRIC HEAT CONTACTORS
24 VAC – 10 VA MAX. PER STAGE
1
2
REE-5002
REHEAT RELAY MODULE
OCCUPIED CYCLE (Central System On).
COLD
UNOCCUPIED CYCLE (Central System Off).
COLD
DATE
8 - 6 - 08
LINE
VOLTAGE
A
– T2 R2 T4 V2
N
H
TERMINAL
T4
BLOCK
DISCONNECT
(OPTIONAL)
GROUND
CONTROLLER
24 VAC
TRANSFORMER
CAPACITOR
FAN
MOTOR
TOTAL AIRFLOW
MIXING
STAGE
TWO
STAGE
MINIMUM
ONE
- 2°F
DAY
(-1.1°C)
SETPOINT
ROOM TEMPERATURE INCREASE
Night Cycle.
INDUCED PLENUM AIR
STAGE
TWO
STAGE
ONE
- 2°F
NIGHT
(-1.1°C)
SETPOINT
ROOM TEMPERATURE INCREASE
B SERIES
SUPERSEDES DRAWING NO.
3500
12 - 2 - 02
TOGGLE
SWITCH
SPEED
C
FAN
RELAY
NO
MAXIMUM
COOLING
HOT
+ 2°F
(+1.1°C)
NO
PRIMARY
AIR
HOT
35SECD-B7