Nailor 37S Manual page 120

Low profile fan powered terminal unit with epic ecm or psc motor
Table of Contents

Advertisement

Sample Diamond Flow Sensor Calibration Label
1.0
.90
.80
.70
.60
.50
.40
.30
.25
.20
.15
.10
.09
.08
.07
.06
.05
.04
.03
.02
30
40
50
60 70
80
100
Application charts for ECM motors
A. Sample VDC vs. CFM Chart
ECM MOTOR FAN CALIBRATION TABLE
CFM vs VDC (Imperial Units)
MODEL SERIES: 35S, 35SST UNIT SIZE 3 - 1/2 H.P. 277 VAC.
FAN POWERED TERMINAL UNIT
CFM
PWM
0-10
CFM
PWM
0-10
VDC
VDC
VDC
VDC
VDC
INPUT
INPUT
0
0
0
480
3.50
2.45
136
0.10
0.06
491
3.60
2.52
144
0.20
0.13
501
3.70
2.59
152
0.30
0.20
512
3.80
2.66
161
0.40
0.27
522
3.90
2.73
170
0.50
0.34
533
4.00
2.80
179
0.60
0.41
543
4.10
2.87
188
0.70
0.48
553
4.20
2.94
197
0.80
0.55
563
4.30
3.01
207
0.90
0.62
573
4.40
3.08
216
1.00
0.69
584
4.50
3.15
226
1.10
0.76
594
4.60
3.22
236
1.20
0.83
603
4.70
3.29
246
1.30
0.90
613
4.80
3.36
256
1.40
0.97
623
4.90
3.43
267
1.50
1.04
633
5.00
3.50
277
1.60
1.11
643
5.10
3.57
288
1.70
1.18
652
5.20
3.64
298
1.80
1.25
662
5.30
3.71
309
1.90
1.32
671
5.40
3.78
319
2.00
1.39
681
5.50
3.85
330
2.10
1.46
690
5.60
3.92
341
2.20
1.53
699
5.70
3.99
352
2.30
1.60
709
5.80
4.06
362
2.40
1.67
718
5.90
4.13
373
2.50
1.75
727
6.00
4.20
384
2.60
1.82
736
6.10
4.27
395
2.70
1.89
745
6.20
4.34
406
2.80
1.96
754
6.30
4.41
416
2.90
2.03
763
6.40
4.48
427
3.00
2.10
772
6.50
4.55
438
3.10
2.17
781
6.60
4.62
448
3.20
2.24
789
6.70
4.69
459
3.30
2.31
798
6.80
4.76
470
3.40
2.38
807
6.90
4.83
THIS UNIT HAS BEEN FACTORY SET AT ____________ CFM.
RE-CALIBRATION IS NOT REQUIRED UNLESS THE ZONE DESIGN AIRFLOW REQUIREMENT HAS CHANGED.
FOR CALIBRATION INSTRUCTIONS, REFER TO BULLETIN WWECM. CAUTION IF CALIBRATING IN SHADED
AREA. AT LOW VOLUMES, VARIATIONS IN FLOW FROM COOLING TO HEATING MAY BE GREATER THAN
5%. AT HIGH VOLUMES, NOISE MAY BE EXCESSIVE.
Page 4 of 6
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
DIAMOND FLOW SENSOR
FIELD CALIBRATION CHART
MODEL SERIES: 3200 (MkII), 35S, 35SST,
35P, 36VRR
150
200
300 400
500
600 800
1000
1500
CFM
Version F, 10.29.01
ECMCT-1
CFM
PWM
0-10
CFM
PWM
0-10
VDC
VDC
VDC
VDC
INPUT
INPUT
816
7.00
4.90
1114
10.50
7.36
824
7.10
4.97
1123
10.60
7.43
833
7.20
5.04
1131
10.70
7.50
841
7.30
5.11
1140
10.80
7.57
850
7.40
5.18
1149
10.90
7.64
859
7.50
5.25
1158
11.00
7.71
867
7.60
5.32
1166
11.10
7.78
876
7.70
5.39
1175
11.20
7.85
884
7.80
5.46
1184
11.30
7.92
893
7.90
5.53
1193
11.40
7.99
901
8.00
5.60
1201
11.50
8.06
909
8.10
5.67
1210
11.60
8.13
918
8.20
5.74
1219
11.70
8.20
926
8.30
5.81
1228
11.80
8.27
935
8.40
5.89
1236
11.90
8.34
943
8.50
5.96
1245
12.00
8.41
952
8.60
6.03
1254
12.10
8.48
960
8.70
6.10
1262
12.20
8.55
968
8.80
6.17
1271
12.30
8.62
977
8.90
6.24
1279
12.40
8.69
985
9.00
6.31
1288
12.50
8.76
994
9.10
6.38
1296
12.60
8.83
1002
9.20
6.45
1305
12.70
8.90
1011
9.30
6.52
1313
12.80
8.97
1019
9.40
6.59
1321
12.90
9.04
1028
9.50
6.66
1329
13.00
9.11
1036
9.60
6.73
1337
13.10
9.18
1045
9.70
6.80
1345
13.20
9.25
1053
9.80
6.87
1353
13.30
9.32
1062
9.90
6.94
1361
13.40
9.39
1071
10.00
7.01
1368
13.50
9.46
1079
10.10
7.08
1376
13.60
9.53
1088
10.20
7.15
1097
10.30
7.22
1105
10.40
7.29
SUBJECT TO CHANGE WITHOUT NOTICE
DFSCC-2
6.98
ALLOWABLE LO SETTING
MIN. ∆P = O.O3" W.G.
2000
3000
4000
6000 8000
B. Sample Application AMP/CFM Chart
2200
2000
1800
1600
1400
1200
1000
800
600
400
0.0
DISCHARGE STATIC PRESSURE, INCHES WG
Application Amperage Data
Unit Size 5 (3/4 H.P. 277V)
MAXIMUM
MINIMUM
0.1
0.2
0.3
0.4
3/05
5
4
3.5
3
2.5
2
1.5
1.0
.75
0.5
IOM-FPTU

Advertisement

Table of Contents
loading

This manual is also suitable for: