CONTROL SEQUENCE B3
COOLING WITH ELECTRIC HEAT AND NIGHT SHUT DOWN
Sequence of Operation:
The terminal fan is interlocked by way of a positive pressure airflow switch, which
automatically energizes the fan upon sensing central system start up.
With room temperature at set point, unit delivers minimum cooling airflow and
maximum induced plenum air. On a rise in room temperature, the thermostat regulates
the controller/actuator to increase primary airflow. As more cold air is supplied to the
fan section, less warm air is induced from the ceiling plenum.
When the room temperature exceeds the setpoint by 2°F (1.1°C) or more, primary
airflow is maintained at the maximum setting. The maximum setting is usually the same
as the total fan volume setting.
On a decrease in room temperature, the thermostat regulates the controller/actuator to
decrease the airflow and as less cold air is supplied to the fan section, more warm air is
induced from the ceiling plenum. If room temperature continues to drop, minimum primary
airflow is maintained and at 0.8°F (0.4°C) below setpoint, the first stage of electric heat is
energized. The optional second heat stage is energized at 1.6°F (0.9°C) below setpoint.
An increase in room temperature de-activates the heat stages at 1.2°F and 0.4°F
(0.7°C and 0.2°C) below setpoint.
Primary airflow is held constant in accordance with thermostat demand. Any changes
in duct air velocity due to static pressure fluctuations are sensed and compensated for,
resulting in pressure independent control.
(Minimum and maximum primary airflow limits are adjusted underneath the thermostat cover).
Unoccupied Cycle (Night Shut Down).
Airflow switch de-energizes fan upon loss of primary (central) air.
Night shut down automatically locks out electric heat.
Options:
Thermostat Scale Plate:
(Thermostat includes backing plate for 2" x 4" electrical box).
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
ANALOG ELECTRONIC CONTROL
FAN POWERED TERMINAL UNIT • SERIES FLOW
CONSTANT VOLUME • PRESSURE INDEPENDENT
MODELS: 35SE, 35SEST, 37SE AND 37SEST B3
CSP-5002
V
N
M
M
N
O
A
I
O
I
O
R
X
N
M
N
U
24V
M
A
METER
T
AC
X
%
RED-CLS
M
GRN-OPN
I
N
C
LED
L
CCW CW
O
S
E
AIRFLOW SWITCH
C
NO
NC
°F or
°C
CTE-5101 ROOM THERMOSTAT (DA)
SINGLE TEMP. SET POINT
12
V1 T3 R1 T1 +
V
A
TERMINAL
V1
T3
T1
+
BLOCK
GROUND
ELECTRIC HEAT CONTACTORS
24 VAC – 10 VA MAX. PER STAGE
1
2
REE-5002
REHEAT RELAY MODULE
OCCUPIED CYCLE (Central System On).
STAGE
TWO
MINIMUM
COLD
- 2°F
(-1.1°C)
UNOCCUPIED CYCLE (Central System Off).
COLD
DATE
8 - 6 - 08
LINE
VOLTAGE
N
H
TOGGLE
DISCONNECT
SWITCH
(OPTIONAL)
SPEED
CONTROLLER
24 VAC
TRANSFORMER
C
FAN
RELAY
NO
CAPACITOR
FAN
MOTOR
TOTAL AIRFLOW
MIXING
STAGE
ONE
SETPOINT
ROOM TEMPERATURE INCREASE
Night Shut Down.
FAN AND
NO
HEAT
PRIMARY
SHUTDOWN
AIR
SETPOINT
ROOM TEMPERATURE INCREASE
B SERIES
SUPERSEDES DRAWING NO.
3500
12 - 2 - 02
MAXIMUM
COOLING
HOT
+ 2°F
(+1.1°C)
HOT
35SECD-B3