CONTROL SEQUENCE A5
COOLING WITH MORNING WARM-UP AND NIGHT SHUTDOWN
Sequence of Operation:
Day/Occupied Cycle:
The terminal fan is interlocked by way of a positive pressure airflow switch, which
automatically energizes the fan upon sensing central system start up.
With room temperature at set point, unit delivers minimum cooling airflow and
maximum induced plenum air. On a rise in room temperature, the thermostat regulates
the controller/actuator to increase primary airflow. As more cold air is supplied to the
fan section, less warm air is induced from the ceiling plenum.
When the room temperature exceeds the setpoint by 2°F (1.1°C) or more, primary
airflow is maintained at the maximum setting. The maximum setting is usually the same
as the total fan volume setting.
On a decrease in room temperature, the thermostat regulates the controller/actuator to
decrease the airflow and as less cold air is supplied to the fan section, more warm air
is induced from the ceiling plenum. If room temperature continues to drop, minimum
primary airflow is maintained. An increase in room temperature reverses the sequence.
Primary airflow is held constant in accordance with thermostat demand. Any changes
in duct air velocity due to static pressure fluctuations are sensed and compensated for,
resulting in pressure independent control.
(Minimum and maximum primary airflow limits are adjusted underneath the thermostat cover).
Unoccupied Cycle (Night Shutdown).
Airflow switch de-energizes fan upon loss of primary (central) air.
Morning Warm-up Cycle.
A duct mounted sensor is used to measure primary air temperature. Upon sensing a
central system supply air temperature above 77°F +/– 4 (25°C +/– 2.2), the primary air
damper will drive fully open regardless of flow limit settings. Central warm air is
delivered to the space.
Options:
Thermostat Scale Plate:
(Thermostat includes backing plate for 2" x 4" electrical box).
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
ANALOG ELECTRONIC CONTROL
FAN POWERED TERMINAL UNIT • SERIES FLOW
CONSTANT VOLUME • PRESSURE INDEPENDENT
MODELS: 35S, 35SST, 37S AND 37SST
CSP-5002
V
N
M
M
N
O
A
I
O
I
O
R
X
N
M
N
U
24V
M
A
METER
T
AC
X
%
RED-CLS
M
GRN-OPN
I
N
C
LED
L
CCW CW
O
S
E
AIRFLOW SWITCH
C
NO
NC
STE-1002
DUCT TEMP. SENSOR
°F or
°C
CTE-5101 ROOM THERMOSTAT (DA)
SINGLE TEMP. SET POINT
12
V1 T3 R1 T1 +
V
A
TERMINAL
V1
T1
+
BLOCK
GROUND
REE-1005
RELAY MODULE
OCCUPIED CYCLE (Central System On).
MINIMUM
COLD
- 2°F
(-1.1°C)
- 2°F
(-1.1°C)
DATE
8 - 6 - 08
LINE
VOLTAGE
N
H
TOGGLE
DISCONNECT
SWITCH
(OPTIONAL)
SPEED
CONTROLLER
24 VAC
TRANSFORMER
C
FAN
RELAY
NO
CAPACITOR
FACTORY
FAN
INSTALLED
MOTOR
JUMPER
TOTAL AIRFLOW
MIXING
SETPOINT
ROOM TEMPERATURE INCREASE
MORNING WARM-UP CYCLE
(Central System On).
MAXIMUM FLOW WITH WARM-UP ACTIVATED
SETPOINT
ROOM TEMPERATURE INCREASE
B SERIES
SUPERSEDES DRAWING NO.
3500
12 - 2 - 02
B2
MAXIMUM
COOLING
HOT
+ 2°F
(+1.1°C)
+ 2°F
(+1.1°C)
35SCD-B2