Nailor 37S Manual page 46

Low profile fan powered terminal unit with epic ecm or psc motor
Table of Contents

Advertisement

IF CONTROLLERS ARE TO BE
NETWORKED TOGETHER, TURN ON
EOL DIP SWITCHES ON THE
CONTROLLERS AT BOTH PHYSICAL
ENDS OF THE NETWORK. CONNECT
SHIELD TO EARTH GROUND
AT ONLY ONE POINT.
FROM
BLK
PREVIOUS
RED
CONTROLLER
SHLD
TO
BLK
NEXT
RED
SHLD
CONTROLLER
STE-6014W36
RJ-45, 25 FT.
ETHERNET CABLE
STE-8001W36/8201W36
STE-1401 DISCHARGE AIR TEMPERATURE SENSOR
10 KΩ, TYPE 3 (FACTORY WIRED AND FIELD INSTALLED)
Room Temperature Sensor Option:
Digital Display (STE-8001W36)
TSD
TSDO Digital Display w/Occupancy
Motion Sensor (STE-8201W36)
Rotary Dial (STE-6014W36)
TSR
CONTROL SEQUENCE N300
Sequence of Operation:
1. Changeover/Morning Warm-up (Central AHU Heat/Cool): If supply air as measured by the discharge
air temperature (DAT) sensor is below 72°F (22.2°C), cool air is said to be available. If supply air is above
76°F (24.4°C), warm air is said to be available.
2. Cool Air Available: As space temperature rises above the cooling setpoint, the controller increases
primary airflow. At a space temperature of 2°F (1.1°C) above the cooling setpoint, maximum cooling
airflow is maintained. On a decrease in space temperature, the controller reduces airflow. Below cooling
setpoint, minimum airflow is maintained.
3. The fan is started during occupied and standby modes and runs continuously at maximum fan speed.
The fan induces warm ceiling plenum air as the primary airflow varies and maintains a constant volume to
the space. During unoccupied mode, the fan starts on a call for heating only. The fan stops only during
unoccupied mode when there is no call for heat. EPIC ECM Motor Only: During standby and unoccupied
modes, the fan runs at minimum fan speed.
4. As the space temperature drops below the heating setpoint, the fan continues to recirculate warm
ceiling plenum air.
5. Warm Air Available: As space temperature drops below the heating setpoint, the controller increases
primary airflow. At a space temperature of 2°F (1.1°C) below the heating setpoint, maximum heating
airflow is maintained. On an increase in space temperature, airflow decreases. As space temperature
rises above the heating setpoint, minimum heating airflow is maintained.
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
EZVAV DIGITAL CONTROLS
SERIES FAN POWERED (CAV) TERMINAL UNIT
COOLING (PLENUM HEAT ONLY)
PRESSURE INDEPENDENT
MODELS: 35S(ST) AND 37S(ST) N300
BAC-8005-36 CONTROLLER
EOL
AIRFLOW SENSOR
–A
+B
S
TOTAL
STATIC
(HIGH)
(LOW)
T-STAT/
SENSOR
MAX. FAN
SPEED
MIN. FAN
SPEED
FAN OFF
EXTERNAL CONNECTIONS:
AI1 = DAT SENSOR
1/4" (6) O.D. TUBING
A04 = FAN SPEED
TO FLOW SENSOR
B05 = FAN ENABLE
H L
NOTES:
1. CONTROLLER SETTINGS MUST BE
INITIALLY SET USING A STE-8XXX.
LINE
VOLTAGE
H
N
24 VAC
FACTORY
WIRING
FAN OPERATION
OCCUPIED
UNOCCUPIED
STANDBY
STANDBY
ROOM TEMP. INCREASE
HTG.
SP
MAX. HTG. CFM
DATE
10 - 20 - 16
EPIC ECM
MOTOR ONLY
FAN
FAN
START
SPEED
24 VAC
MIN. -100%
0 – 10 VDC
+
COM ~
FIELD
WIRING
COLD AIR AVAILABLE SEQUENCE
TOTAL AIR FLOW
MAX. COOLING CFM
INDUCED AIR
MINIMUM COOLING CFM
CLG. SPAN ROOM TEMP. INCREASE
HTG.
CLG.
+2°F
SP
SP
(+1.1°C)
WARM AIR AVAILABLE SEQUENCE
TOTAL AIR
INDUCED AIR
MINIMUM HEATING CFM
HTG. SPAN
ROOM TEMP. INCREASE
-2°F
HTG.
CLG.
(-1.1°C)
SP
SP
B SERIES
SUPERSEDES DRAWING NO.
3500
12 - 2 - 15
D35N300

Advertisement

Table of Contents
loading

This manual is also suitable for:

37sw37se

Table of Contents