DESCRIPTION:
• Only 11" (279) high.
• 20 ga. (1.0) galvanized
steel construction.
• 16 ga. (1.6) galvanized
steel inclined blade damper.
45° rotation. CW to close.
• Multi-point
averaging
Diamond Flow sensor.
• Access panels top and
bottom.
• 1/2"
(13)
dual
density
insulation, exposed edges
coated
to
prevent
air
erosion. Meets requirements
of NFPA 90A and UL 181.
• Single
point
electrical
and/or pneumatic main air
connection.
• Discharge
opening
for
flanged duct connection.
• Full
primary
air
valve
low voltage NEMA 1 type
enclosure
for
factory
mounted DDC and analog
electronic controls.
• Controls
mounted
as
standard on RH side as
shown. Terminals ordered
with LH controls (optional)
are inverted.
MOTOR OPTIONS:
q
Energy
efficient
PSC
fan motor with overload
protection. Solid state
fan speed controller with
minimum voltage stop.
q
Ultra-high efficiency ECM
fan
motor.
EPIC
fan
volume controller.
OPTIONS:
q
Filter frame and 1" (25)
disposable filter.
q
Toggle disconnect
switch.
q
Steri-liner.
q
Fiber-free liner.
q
Solid metal liner.
q
Perforated metal liner.
Fan unit fusing.
q
q
Hanger brackets.
q
Left-hand controls
location.
q
FN2 90° Line Voltage
Enclosure.
q
FN3 Remote Line
Voltage Enclosure
(see submittal FN3).
q
Special features
____________________.
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
LOW PROFILE FAN POWERED TERMINAL UNIT WITH
EPIC ECM OR PSC MOTOR
SERIES FLOW • CONSTANT OR VARIABLE VOLUME
MODELS: 37S, 37SW AND 37SE • UNIT SIZE 4
Model 37S and Basic Unit
IH
OPTIONAL
INDUCED AIR
INLET FILTER
IW
MULTI-POINT
FLOW
SENSOR
PRIMARY
NOM. – 1/8" (3)
AIR
DRIVESHAFT
PRIMARY
AIR
Dimensional Data
Electrical Data
The EPIC ECM is a variable horsepower motor.
*
Refer to Selectworks schedule for actual power consumption.
FLA = Full load amperage. All motors are single phase/60 Hz.
INDUCED
AIR
W
2
INDUCED
AIR
5 3/4" (146)
14"
(356)
OPTIONAL
90° FN2 HINGED
FAN CONTROLS
ENCLOSURE
OPTIONAL
HINGED FAN
PRIMARY AIR
CONTROLS
VALVE CONTROLS
ENCLOSURE
H
ENCLOSURE
2
5 1/2"
(140)
DATE
8 - 13 - 19
L
P
FAN
W
FAN
15"
10"
(381)
(254)
6 3/4"
(171)
11" (279)
Page 1 of 2.
For heat options; see page 2.
Dimensions are in inches (mm).
B SERIES
SUPERSEDES DRAWING NO.
3700
7 - 18 - 17
DH
11 1/4"
(286)
DW
11 1/4"
(286)
B
11" (279)
37S-2

Advertisement